SYSTEM TEMP LOW

This alarm indicates that the temperature inside the controller is below -10 °C.
Possible Cause

Correction Action

Low ambient temperatures

Provide heat for the controller

SYSTEM TEMP HIGH

This alarm indicates that the temperature inside the controller is above 75 °C.
Possible Cause

Correction Action

High ambient temperatures

Provide cooling for the controller

DISPLAY ERROR

This alarm occurs if the user interface gets lost
Possible Cause

Correction Action

Pressing keys very quickly

Exit out of the screen and continue programming

CONTROLLER, POWER, DISPLAY, OR SENSOR BOARD ERROR

This alarm occurs if the board listed is not recognized

Possible Cause

Correction Action

Poor ribbon cable connection

Remove and reseat ribbon cable, cycle power

Faulty board

Return the controller for repair

CONTROLLER, POWER, SENSOR, DISPLAY, NETWORK OR ANALOG OUTPUT BOARD VARIANT

This alarm occurs if the type of board that is detected is not a valid type
Possible Cause

Correction Action

Poor ribbon cable connection

Reseat ribbon cable

Faulty ribbon cable

Replace ribbon cable

Faulty Board

Replace the board listed in the error message

INVALID CONTROL MODE

  

This alarm occurs if the programmed control mode is not possible for the installed power relay board
Possible Cause

Correction Action

The power relay board has been removed and 

replaced with an incorrect model

Reinstall the correct board or reprogram the output to a valid type 

for the board installed

SENSOR, DIGITAL INPUT, RELAY OR ANALOG OUTPUT DISABLED

  

This alarm occurs if software for that input or output did not start correctly
Possible Cause

Correction Action

The software is not functioning

If the error message clears on its own, no action is required.
If the error message persists, cycle power.
If the error message still persists, return the controller for repair.

RELAY OR ANALOG OUTPUT CONTROL FAILURE 

This alarm occurs if software for that output did not run correctly
Possible Cause

Correction Action

The software is not functioning

If the error message clears on its own, no action is required.
If the error message persists, cycle power.
If the error message still persists, return the controller for repair.

FRAM FILE SYSTEM ERROR

  

This alarm occurs if the FRAM is not detected at power up
Possible Cause

Correction Action

The FRAM was or is not functioning

If the error message clears on its own, no action is required.
If the error message persists, cycle power.
If the error message still persists, replace the controller board.

8.0  SERVICE POLICY

Walchem controllers have a 2-year warranty on electronic components and a 1-year warranty on mechanical parts and 

electrodes.  See Statement of Limited Warranty in front of manual for details.

Walchem controllers are supported by a worldwide network of authorized master distributors.  Contact your authorized 

Walchem distributor for troubleshooting support, replacement parts, and service.  If a controller is not functioning 

properly, circuit boards may be available for exchange after the problem has been isolated.  Authorized distributors will 

provide a Return Material Authorization (RMA) number for any products being returned to the factory for repair.  Re-

pairs are generally completed in less than one week.  Repairs that are returned to the factory by next-day-air freight will 

receive priority service.  Out-of-warranty repairs are charged on a time and material basis.

Содержание WTCW100 Series

Страница 1: ...Five Boynton Road Hopping Brook Park Holliston MA 01746 USA TEL 508 429 1110 WEB www walchem com WCT WBLW100 Series Cooling Tower and Boiler Controller Instruction Manual...

Страница 2: ...onents are expendable and are not covered by any warranty THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTY EITHER EXPRESS OR IMPLIED AS TO DESCRIP TION QUALITY MERCHANTABILITY FITNESS FOR ANY PARTICULAR...

Страница 3: ...time Daily Weekly 2 week or 4 week Biocide timers with pre bleed and post add lockout of bleed Intermittent sampling for boilers with proportional blowdown controlling on a trapped sample Time Proport...

Страница 4: ...lly isolated 600 Ohm max resistive load Resolution 0 0015 of span Accuracy 0 5 of reading Agency Approvals Safety UL 61010 1 2012 3rd Ed CSA C22 2 No 61010 1 2012 3rd Ed IEC 61010 1 2010 3rd Ed EN 610...

Страница 5: ...sensor range High end of sensor range Sample period Time Proportional mode 10 seconds 3600 seconds Sample Time Intermittent Sampling mode 0 seconds 3600 seconds Hold Time Intermittent Sampling mode 0...

Страница 6: ...1 Determine the Rate of Steam Production in Pounds per Hour Either read off the boiler name plate water tube boilers or Calculate from horsepower rating fire tube boilers HP x 34 5 lbs hr Example 100...

Страница 7: ...graphs on the next page Use of a flow control valve will give you the best control of the process since the flow rate can be easily adjusted The dial on the valve also gives you a visual indication if...

Страница 8: ...nside the controller even when the power switch on the front panel is in the OFF position The front panel must never be opened before power to the controller is REMOVED If your controller is prewired...

Страница 9: ...Union To Drain To Drain 1 2 3 Figure 4 Typical Boiler Installation Continuous Sampling Install accessories either vertically or horizontally per manufacturer s instructions To Drain Skimmer Blowdown L...

Страница 10: ...10 VOLT AC OUTLET TO SANITARY SEWER COOLING TOWER OPEN SUMP CIRCULATION PUMP X Unions installed for replacement of solenoid or strainer Y Y strainer Z solenoid TYPICAL INSTALLATION SUBMERSION ELECTROD...

Страница 11: ...ivity Electrode TEMP WHT TEMP GRN RCV BLK SHIELD XMT RED SAFETY COVER LABEL R SHLD High Pressure Conductivity Electrode GRN WHT RED BLK Condensate Electrode wiring is typical of all three sensor optio...

Страница 12: ...Effect Flow Meter SHIELD INPUT POWER Chart Recorder SIGNAL SHIELD SHIELD R SHLD Figure 10 Digital Input and Analog Output Wiring 1 2 3 4 5 6 7 8 9 10 11 12 TB2 TB1 FUSE POWER SWITCH POWER SWITCH 1 2 3...

Страница 13: ...U 240V BLK 120V BRN 240V Figure 12 W110 AC Power Relay Output Wiring 1 2 3 4 5 6 7 8 9 10 11 12 TB2 TB1 FUSE POWER SWITCH POWER SWITCH 1 2 3 4 5 6 7 8 9 10 11 12 R1 R2 R3 N N N N L TB3 TB4 TB5 TB6 TB7...

Страница 14: ...er or Lower keys Once the value of the number is correct use the Enter key to store the new value into memory or use the Cancel key to leave the number at its previous value and go back Changing Names...

Страница 15: ...ghted Press the Enter key Press the Scroll Down key until your language is highlighted Press the Confirm key to change all menus to your language Set date if necessary Press the Scroll Up key until Da...

Страница 16: ...ng Setpoint Int Sampling R1 HOA Setting Setpoint Manual R1 HOA Setting Interlock Channels Pulse Prop R1 HOA Setting Setpoint Dual Setpoint R1 HOA Setting Setpoint Probe Wash R1 HOA Setting Input Timer...

Страница 17: ...ter key to get to the Details screen Press the Settings key If the name of the relay does not describe the control mode desired press the Scroll Down key until Mode is highlighted Press the Enter key...

Страница 18: ...ure compensation Enter the temperature of the buffer and press Confirm Buffer Value only appears for One Point Calibration except when automatic buffer recognition is used Enter the value of the buffe...

Страница 19: ...e next reading shown will consist of an average of 10 of the previous value and 90 of the current value Cable Length The controller automatically compensates for errors in the reading caused by varyin...

Страница 20: ...ress the Enter key with an output highlighted to access that output s details and settings NOTE When the output control mode or the input assigned to that output is changed the output reverts to OFF m...

Страница 21: ...and a conductivity limit are set the time limit takes precedence The bleed relay will turn off once the time limit is reached or when the prebleed conductivity limit is reached whichever occurs first...

Страница 22: ...ion from the set point The relay goes through a sequence of activation deactivation as described below The intended purpose of this algorithm is boiler blowdown A sample cannot be supplied to the sens...

Страница 23: ...ontrol Mode Basic Timer Operation When a Probe Wash event triggers the algorithm will activate the relay for the programmed time The relay will activate a pump or valve to supply a cleaning solution t...

Страница 24: ...digital flow meter and continuously adjusts the analog 4 20 mA output proportional band to achieve a target PPM level The user enters the target PPM and the data necessary to calculate the proportiona...

Страница 25: ...troller see Export User Config file below Press the Enter key and then press the Confirm key to transfer those settings to this controller Export User Config File The User Configuration file contains...

Страница 26: ...ays have a fuse to protect the controller from devices connected to the relays that draw excessive current Locate the fuse on the circuit board at the back of the controller enclosure underneath the c...

Страница 27: ...ible Cause Corrective Action No flow Check piping for closed valves blockage etc Check recirculation pump Faulty flow switch cable Check with ohmmeter Faulty controller Check by shorting digital input...

Страница 28: ...ectly Possible Cause Correction Action The software is not functioning If the error message clears on its own no action is required If the error message persists cycle power If the error message still...

Страница 29: ...57 Control Board with AO 191613 Ribbon Cable Controller Parts 103875 Panel 102961 Hanger 102586 Nut 190998 03 Switch assembly 3 ft cable 190996 Float 102919 O Ring 191020 03 Switch Float Assembly 3 ft...

Страница 30: ...191638 03 Electrodeless Conductivity sensor CPVC 3 ft cable 102586 Nut 102594 O ring 191020 03 Flow switch assembly 3 ft cable 190997 03 Switch Float assembly 3 ft cable 102594 O ring 102881 Flow swi...

Страница 31: ...Switch manifold on panel C High pressure contacting conductivity D High pressure contacting cond Flow Switch manifold on panel E Inline submersion 316SS contacting conductivity F 316SS contacting cond...

Отзывы: