200 Diagnostics
WAGO-I/O-SYSTEM
750
758-874/000-131
WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Pos: 51.5 /Serie 758 (Funk, IPC und PFC)/Diagnose/Diagnose LED-Signalisierung 758-87x Tabelle 1_1 DPM @ 10\mod_1312535342005_21.doc @ 76011 @ @ 1
Table 72: I/O-IPC Operational Messages
Position LED
Color/Status
Cause
Explanation/Remedy
Yellow
-
I/O-IPC is ready for
operation.
41 RDY
Green flashing
(irregular)
There is a system
error in the
PROFIBUS
controller.
Restart the I/O-IPC. If
this malfunction
recurs, contact
WAGO support.
Green The
I/O-IPC
has
established at least
one connection to a
configured
PROFIBUS slave.
-
You have stopped
communication with
the slave (ERR LED
also lights up).
-
Green flashing
(5 Hz)
The I/O-IPC cannot
communicate with the
slaves.
Check the cables to
the slaves and check
these for
malfunctions.
42 RUN
Green flashing
(irregular)
There is a missing or
defective
configuration of the
PROFIBUS or a time
error of the host
watchdog has
occurred.
Check the CoDeSys
configuration.