WAGO-I/O-SYSTEM 750
Appendix 269
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Table 141: Description of the configuration scripts for "MODBUS"
Parameter
Status Call
Output/Input
Validity
MODBUS
MODBUS/UDP
read
get_rts3scfg_value
MODBUS_UDP state
Status of MODBUS/UDP:
enabled
disabled
MODBUS/UDP
Status
write
change_rts_config
area=MODBUS_UDP
state=<value>
Enable/disable the
MODBUS/UDP server.
Entries for <value> are:
enabled
disabled
immediate
MODBUS/TCP
read
get_rts3scfg_value
MODBUS_TCP state
Status of MODBUS/TCP:
enabled
disabled
MODBUS/TCP
Status
write
change_rts_config
area=MODBUS_TCP
state=<value>
Enable/disable the
MODBUS/TCP server.
Entries for <value> are:
enabled
disabled
read
get_rts3scfg_value
MODBUS_TCP
TCPTimeout
Timeout value for
MODBUS/TCP
Timeout (msec)
write
change_rts_config
area=MODBUS_TCP
timeout=<value>
Here, set the time period
(timeout) for the
MODBUS/TCP connection
(ms), after which the
connection is automatically
ended during a break in
communication.
immediate
MODBUS/RTU
read
get_rts3scfg_value
MODBUS_RTU state
Status of MODBUS/RTU.
Entries for <value> are:
enabled
disabled
State
write
change_rts_config
area=MODBUS_RTU
timeout=<value>
Enable/disable the
MODBUS/RTU server.
Entries for <value> are:
enabled
disabled
read
get_rts3scfg_value
MODBUS_RTU
Node_ID
Node ID for
MODBUS/RTU
Node ID
write
change_rts_config
area=MODBUS_RTU
node-id=<value>
Node ID (number) for
MODBUS/RTU
Specify the node-ID for
<value>
read
get_rts3scfg_value
MODBUS_RTU Timeout
Timeout value for
MODBUS/RTU
Timeout (msec)
write
change_rts_config
area=MODBUS_RTU
Timeout=<value>
Change timeout value (ms)
for MODBUS/RTU.
Specify the timeout value in
ms for <value>.
immediate