WAGO-I/O-SYSTEM 750
I/O Modules 251
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
18.2.6
System Modules
18.2.6.1 System Modules with Diagnostics
750-610, -611
The modules provide 2 bits of diagnostics in the Input Process Image for
monitoring of the internal power supply.
Table 125: System Modules with Diagnostics 750-610, -611
Input Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnostic
bit S 2
Fuse
Diagnostic
bit S 1
Fuse
Pos: 60.19 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Mapping/ETHERNET - EtherNet/IP - MODBUS/TCP/PA ETHERNET - MODBUS TCP Teil 3 Binäre Platzhalterklemmen - letzte Klemme @ 8\mod_1279182270905_21.doc @ 60020 @ 4 @ 1
18.2.6.2 Binary Space Module
750-622
The Binary Space Modules behave alternatively like 2 channel digital input
modules or output modules and seize depending upon the selected settings 1, 2, 3
or 4 bits per channel. According to this, 2, 4, 6 or 8 bits are occupied then either in
the process input or the process output image.
Table 126: Binary Space Module 750-622 (with behavior like 2 channel digital input)
Input and Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
(Data bit
DI 8)
(Data bit
DI 7)
(Data bit
DI 6)
(Data bit
DI 5)
(Data bit
DI 4)
(Data bit
DI 3)
Data bit
DI 2
Data bit
DI 1
Pos: 61 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1