WAGO-I/O-SYSTEM 750
CoDeSys 2.3 Runtime Environment 115
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Figure 15: Creating a new communication channel (RS 232) 2
6.
Enter the following communication parameters of the RS-232 interface:
•
Baud rate: 115200 bit/sec
•
Parity:
Even
•
Stop Bits: 1
•
Motorolla Byteorder: No
•
Flow Control: Off
7.
Transfer the PLC programs by clicking on
Online
in the menu bar and
select
Login
.
8.
Remember that the I/O-IPCs Run/Stop switch must be in the "Run" position.
9.
Start the PLC program by clicking on
Online
in the menu bar and selecting
Run
.