I/O Modules
•
173
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.1.9
4 DO I/O Modules
Module
Identification
hex
Identification
dec
750-504, 750-516, 750-519, 750-5dd 4 DO,
Buerkert 8644 monost. 3 DO, Buerkert 8644 monost. 4 DO,
Buerkert 8644 bistab. 4 DO
0x20 32
*750-504, *750-516, *750-519, *750-5dd 4 DO,
*Buerkert 8644 monost. 3 DO, *Buerkert 8644 monost. 4 DO,
*Buerkert 8644 bistab. 4 DO
0x00 0
Process Image
Input Image
in [Bit]
Output Image
in [Bit]
Internal bus
0
4
PROFIBUS DP
0
4
PFC (CPU)
0
4
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is
plug
fitted
*)
- supplied to the I/O module
not plug fitted
- ignored by the coupler
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug
0 0 0 0 1
1
7 6 5 4 3 2 1 0
0 0 0 0 0 0 1 0
2
7 6 5 4 3 2 1 0
0 0 0 0
SV3 SV2 SV1 SV0
PFC
6
0
1
Module is mapped into the field bus PA and PFC-PA
Module is exclusively mapped into the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SV0
0
Substitute channel 1
SV0
1
Substitute channel 2
SV0
2
Substitute channel 3
SV0
3
Substitute channel 4
Italic
cannot be changed