174 • I/O Modules
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM
750
Bus System
5.4.1.10 4 DO I/O Modules with 1 Bit Diagnostics per Channel
Module
Identification
hex
Identification
dec
750-532, 750-5dd 4 DO/4 DIA-DI/DIA,
Diagnostics in the input process image
0x30 48
750-532, 750-5dd 4 DO/4 DIA
0x20
32
*750-532, *750-5dd 4 DO/4 DIA
0x00
0
Process Image
Input Image
in [Bit]
Output Image
in [Bit]
Internal bus
4
4
Diagnostics in the input process image
Yes 4
4
PROFIBUS DP
No 0
4
PFC (CPU)
4
1)
(0
2)
) 4
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is
plug
fitted
*)
- supplied to the I/O module
not plug fitted
- ignored by the coupler
Diagnostics is mapped into the
Input-PAB
The diagnostics information of the I/O module
is
(only for *-Modules)
released
- mapped into the input process image
locked
*)
- not mapped into the input process image
Diagnostics channel x
The diagnostics information of the correspond-
ing channel is
released
- transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
Substitute channel x
0
*)
1
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault.
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug
PA-
Diag
0 0 0 1
1
7 6 5 4 3 2 1 0
0 0 0 1 1 0 1 1
2
7 6 5 4 3 2 1 0
SV3
Diag
En3
SV2
Diag
En2
SV1
Diag
En1
SV0
Diag
En0