200 • I/O Modules
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM
750
Bus System
5.4.7 ENOCEAN Receiver Module
Module
Register Communication
possible
Identification
hex
Identification
dec
Yes 0xB3
179
750-642
No (not possible)
-
-
Process Image
Input Image
in [Byte]
Output Image
in [Byte]
Internal bus
6
6
Register communication
possible
Yes 4
4
PROFIBUS DP
No (not possible)
-
-
PFC (CPU)
4
4
Parameter
Value
Meaning
I/O module is physically
The I/O module process data is
plug
fitted
*)
- supplied by the I/O module or
supplied to the I/O module
not plug fitted
- set to zero by the coupler or
ignored by the coupler
Diagnostics channel x
The diagnostics information of the correspond-
ing channel is
released
- transmitted to PROFIBUS DP master
locked
*)
- not transmitted to PROFIBUS DP master
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0
PFC
Plug
0 0
Diag
En0
0 0
1
7 6 5 4 3 2 1 0
1 1 0 0 1 1 0 0
2
15 14 13 12 11 10 9 8
reserved
3
7 6 5 4 3 2 1 0
reserved
PFC
6
0
1
Module is mapped in the field bus and PFC-PA
Module is exclusively mapped in the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
DiagEn0
2
0
1
Diagnostics locked (default)
Diagnostics released
Italic
Cannot be changed