I/O Modules
•
145
Design of the Process Data for PROFIBUS-DP
WAGO-I/O-SYSTEM 750
Bus System
5.2.21 SSI Encoder Interface
750-630
Process Image Length in [Byte]
Register communication possible
Input
Output
Yes 6
6
No 4
0
Mapping with Register Communication (Alternative Format, Default Setting)
Data format
MOTOROLA
INTEL
I/O
area
Input Output Input Output
S0 C0 S0 C0
D1 D1 D0 D0
D0 D0 D1 D1
- - - -
D3 D3 D2 D2
Channel 1
D2 D2 D3 D3
Mapping with Register Communication (Standard-Format)
Data format
MOTOROLA
INTEL
I/O
area
Input Output Input Output
S0 C0 S0 C0
- - - -
D3 D3 D0 D0
D2 D2 D1 D1
D1 D1 D2 D2
Channel 1
D0 D0 D3 D3
Mapping without Register Communication
Data format
MOTOROLA
INTEL
I/O
area
Input Output Input Output
D3 - D0 -
D2 - D1 -
D1 - D2 -
Channel 1
D0 - D3 -