120 • Programmable Field Bus Controller 750-833
Technical
Data
WAGO-I/O-SYSTEM
750
Bus System
3.13 Technical Data
System Data
Number of I/O modules
96 with repeater
Number of I/O points
ca. 6000 (master dependent)
Transfer medium
Cu cable acc. EN 50170
Bus segment length
100 m ... 1200 m
(baud rate dependent / cable dependent)
Transmission rate
9.6 kbaud ... 12 Mbaud
Transmission time for 10 modules
each with 32 DI and 32 DO
typ. 1 ms
max. 3.3 ms
Bus connection
1 x D-Sub 9; female
Programming
IEC 61131-3
WAGO-I/O-
PRO
AWL, KOP, FUP, ST, AS
Technical Data
Number of I/O modules
63
Protocol
DP / DPV1
Field bus
- Input process image
- Output process image
max. 244 byte (128 byte up to SW 02)
max. 244 byte (128 byte up to SW 02)
Configuration
via PC or controls
Voltage supply
DC 24 V (-15 % / + 20 %)
Input current
max
500 mA at 24 V
Internal system supply module
efficiency
87 %
Internal current consumption
200 mA at 5 V
Total current for I/O modules
1800 mA at 5 V
Voltage via power jumper contacts
DC 24 V (-15 % / + 20 %)
Current via power jumper contact
max
DC 10 A
Dimensions w x h* x l
*from upper edge of DIN 35 rail
51 mm x 65 mm x 100 mm
Weight
ca. 195 g
Standards and Regulations
PROFIBUS-Norm
EN 50 170
EMC-Immunity to interference (CE)
acc. to EN 50082-2 (96)
EMC-Emission of interference (CE)
acc. to EN 50081-2 (94)