765-1205/100-000
Commissioning
56
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
10
Commissioning
Note
The figures and descriptions below are an example configuration
The figures and descriptions this section contains are based on an example configura-
tion.
Your configuration, and thus the content shown, may differ from the content illustrated
here.
10.1 Getting the IP Address from the EtherCAT Master
The module requires an IP address if IP-based communication is to be used. This is the
case, for example, if the WAGO I/O Field Webserver or the OPC UA server of the module
is used. The module has no IP address when delivered. The module gets the IP address
from the EtherCAT
®
master.
The module does not need an IP address if it is to communicate with the master exclu-
sively via EtherCAT
®
.
Setting the IP address for the Module for the EtherCAT
®
Master
You can set the IP address for the module in the configuration software of the EtherCAT
®
master, e.g., TwinCAT. To do so, create a configuration project as described under
8
1. Open the configuration software of the EtherCAT
®
master.
2. Open the window with the EtherCAT
®
properties of the WAGO module.
3. Open the advanced settings.
4. Select Mailbox > EoE (Ethernet over EtherCAT).
ð
The window for setting the IP address (for the module) is displayed.
5. Enter the IP address, the subnet mask and the IP address of the default gateway
(typically the default gateway is the IP address of the EtherCAT
®
master).