765-1205/100-000
Diagnostics
110
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
IO-Link Event Code Description
Remedy
0x180E
P24 (class B) missing or has under-
voltage
Check power supply
0x180F
Short circuit on P24 (class B)
Check wiring (e.g., 2L+)
0x1810
Short circuit on I/Q
Check wiring
0x1811
Short circuit on C/Q
Check wiring
0x1812
Overcurrent on I/Q
Check load
0x6000
Invalid cycle time
Check port configuration parameters
0x6001
Revision error (incompatible protocol
version)
Check port configuration parameters
0x6002
ISDU batch failed
Fix parameter inconsistency
11.2.1.11 Events Triggered by the IO-Link Device
Events can also be triggered by an IO-Link device connected to the IO-Link master via a
port. An IO-Link device sends the “Event Code” and the “Event Qualifier” of the event to
the IO-Link master.
The following values are set in the event qualifier:
TYPE = 1 (Notification
MODE = 1 (Single shot)
SOURCE = 0 (Device/remote)
The IO-Link master sends this event to the EtherCAT slave, which can report it to the
EtherCAT master as an emergency. The IODD of the IO-Link device contains manufac-
turer-specific events with message text.
The following table describes possible standard events of the IO-Link device that can trig-
ger EtherCAT emergencies.
Table 79: Standard Events of the IO-Link Device
IO-Link Event Code Description of the Error Function
on the Connected IO-Link Device
Corrective Action on the Connected
IO-Link Device
0x1000
General malfunction
IO-Link device reports unknown error
0x4000
Temperature error
Eliminate overload
0x4210
Device overheating
Eliminate heat source
0x4220
Device undercooling
Insulate IO-Link device
0x5000
Hardware error in device
Replace IO-Link device
0x5010
Malfunction of a component
Repair for replacement
0x5011
Loss of data of non-volatile memory
Check batteries
0x5012
Batteries too weak
Replace batteries
0x5100
General error in the power supply
Check availability
0x5101
Fuse blown/open
Replace fuse
0x5110
Overvoltage in primary power supply
Check tolerance
0x5111
Undervoltage in primary power supply Check tolerance
0x5112
Error in additional power supply
Check tolerance
0x6000
Error in device software
Check firmware version
0x6320
Parameter error
Check datasheet and values
0x6321
Missing parameter(s)
Check datasheet
0x6350
Parameter change
Check configuration
0x7700
Wire break on a lower-level device
Check installation