765-1205/100-000
Diagnostics
Product manual | Version: 2.0.0
111
8DIO FLD EC DC 24V 2.0A
IO-Link Event Code Description of the Error Function
on the Connected IO-Link Device
Corrective Action on the Connected
IO-Link Device
0x7701 – 0x770F
Wire break of lower-level device
1...15
Check installation
0x7710
Short circuit
Check installation (device)
0x7711
Grounding fault
Check installation
0x8C00
Technology-specific application error
Reset device
0x8C01
Simulation active
Check operating mode
0x8C10
Value range of a process variable ex-
ceeded
Process data insecure
0x8C20
Measurement overrange
Check application
0x8C30
Process variable value below value
range
Process data insecure
0x8C40
Maintenance required
Cleaning
0x8C41
Maintenance required
Refill
0x8C42
Maintenance required
Replacement of wear parts
11.2.2 Error Register
The error register can be accessed in the object dictionary of the EtherCAT
®
slave under
index 0x1001.
Table 80: Error Register (Index 0x1001)
Index
Name
Explanation
Type
Flag
Default
0x1001
Error Register
Error Register Object
Bit 0 = 1: Generic error
Bit 1 = 1: Current error (SSC or
ASC)
Bit 2 = 1: Voltage error (LVS or
LVA)
Bits 3–6: reserved
Bit 7 = 1: Internal module error
(IME)
UINT32
RO
0x00000000