background image

WAGO-TO-PASS® 761 

WAGO TO-PASS® Web  127 

761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485 

 

 

Manual 

 

Version 1.0.0  

 

The calculations for longitudes/latitudes (see below) refer to the format as 
transmitted in the NMEA data (ccmm.mmmm with cc = degree, mm.mmmm = 
Angular minute). The cc.mm format is used to indicate the direction (also 
according to NMEA definition). 
 
Calculating values for LPDx: 

Latitude: 5217.9860N 

 52 * 60 + 17 = 3137 = 0xC41,  

9860 = 0x2684 

 C41;2684;N; 

Longitude: 00855.2699E 

 8 * 60 + 55 = 535 = 0x217,  

2699 = 0xA8B 

 217;A8B;E; 

Horizontal accuracy: 4.4 

 4.4 * 10 = 44 = 0x2C 

 2C; 

Altitude in m: 51.5 

 51.5 * 10 = 515 = 0x203 

 203; 

Position accuracy: 2 

 2; 

Direction: 309.35 

 309 x 60 + 35 = 18575 = 0x488F 

 488F; 

Speed in km/h: 3.7 

 3.7 * 10 = 37 = 0x25 

 25; 

Speed in knots: 2.0 

 2.0 * 10 = 20 = 0x14 

 14; 

Number of satellites: 6 

 6 = 0x6 

 6 

Deviation in km: 0.03 

 0.03 * 100 = 3 = 0x3 

 3 

 
Recalculating values from LPDx: 

Latitude: C41;2683;N; 

 0xC41 = 3137 

 3137 / 60 = 52 Rest 17,  

0x2683 = 9859 

 5217.9859N 

Longitude: 217;AD0;E; 

 0x217 = 535 

 535 / 60 = 8 Rest 55,  

0xAD0 = 2768 

 855.2768E 

Horizontal accuracy: 14; 

 0x14 = 20

 20 / 10 = 2.0 

Altitude in m: 17E; 

 0x17E = 382 

 382 / 10 = 38.2 

Position accuracy: 3; 

 0x3 = 3 

Direction: F92; 

 0xF92 = 3986 

 3986 / 60 = 66 Rest 26 

 66.26 

Speed in km/h: 2E; 

 0x2E = 46 

 46 / 10 = 4.6 

Speed in knots: 18; 

 0x18 = 24 

 24 / 10 = 2.4 

Number of satellites: 6; 

 0x6 = 6 

Deviation in km: 51; 

 0x51 = 81 

 81 / 100 = 0.81 

 

 

 

 

Содержание 761-217

Страница 1: ...Manual WAGO TO PASS 761 Telecontrol Module Compact 8 AI Web MODBUS485 761 217 Telecontrol module for fault detection indication monitoring and remote control Version 1 0 0...

Страница 2: ...one 49 0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can neve...

Страница 3: ...urce GPL 12 2 4 Block Rounding for GPRS Connections 12 2 5 Safety Advice Precautions 13 3 Device Description 16 3 1 Scope of Delivery 16 3 2 Use 16 3 3 View 18 3 4 Connectors 19 3 4 1 Antenna 19 3 4 2...

Страница 4: ...2 Voltage Measurement 44 5 2 4 Digital Outputs 45 5 2 5 Analog Outputs 46 5 2 5 1 Current Measurement 46 5 2 5 2 Voltage Measurement 47 5 2 6 MODBUS Interface 48 5 2 6 1 MODBUS Coupler Controller RS...

Страница 5: ...ram 98 8 2 2 1 Inputs Outputs 99 8 2 2 2 Counters 100 8 3 Acknowledging Error Messages 101 8 4 Switching to Standby 102 8 5 Displaying the Data Logger DSP 103 8 6 Displaying the Event Logger ESP 105 9...

Страница 6: ...a Format for LIOx Variable 125 10 3 2 2 2 Data Format for LPDx Variable 125 10 3 2 2 3 Example for Logger Script Extension 126 10 3 2 3 Logger Script FW 2 33 Counter Inputs 128 10 3 2 3 1 Data Format...

Страница 7: ...ions are included if applicable 1 1 Validity of this Documentation This documentation is only applicable to the telecontrol module 761 217 Telecontrol Module Compact 8 AI Web MODBUS485 1 2 Copyright T...

Страница 8: ...Indicates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if no...

Страница 9: ...out this Documentation 9 761 217 Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 Additional Information Refers to additional information which is not an integral part of this docume...

Страница 10: ...s and data files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item f...

Страница 11: ...dge in automation The specialists must be familiar with the current norms and guidelines for the devices and automated environments All changes to the controller should always be carried out by qualif...

Страница 12: ...ith Open Source GPL The TO PASS Compact telecontrol module firmware contains Open Source software under GPL According to Section 3b of GPL we offer you the source code You can obtain the source code w...

Страница 13: ...installation repair or maintenance work Installation only in appropriate housings cabinets or in electrical operation rooms TO PASS telecontrol modules are exposed operating equipment They may only be...

Страница 14: ...3 dBi Only qualified staff can install and maintain the TO PASS remote module and its antenna The transmitted must be off when working on or nearer to the antenna than specified below HF Exposition T...

Страница 15: ...ents in an enclosure being resistant to the above mentioned materials Clean tools and materials are imperative for handling devices modules Cleaning only with permitted materials Clean soiled contacts...

Страница 16: ...nection of signals from plants transmission preparation of values for the operator TO PASS telecontrol modules 761 217 may be used as fault indicator remote data request system data memory event logge...

Страница 17: ...pt version Standard Extended Extended Parameterizable Time request script Not implemented Not implemented Not implemented Implemented Counter inputs Not supported Not supported Not supported Supported...

Страница 18: ...Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 3 3 View Figure 1 Front view Position Description 1 SIM Card insert 2 Antenna connection 3 Statusindication 4 PC interface 5 Connecti...

Страница 19: ...Connectors 3 4 1 Antenna The screw connector SMA socket for the GSM antenna is located at the top of the housing Figure 2 Antenna connection Observe the maximum length of the antenna cable The total...

Страница 20: ...er source LPS requirements per DIN EN 60950 1 Table 4 Terminal assignment for operating voltage Figure 3 Terminal assignment for operating voltage Connection Short name Designation 1 2 Uv Operating vo...

Страница 21: ...e is constructively no direct conduction connection between the cabinet frame or machine parts and the carrier rail Here the earth ground must be set up via an electrical conductor accordingly valid n...

Страница 22: ...und To achieve this connect the shield over a large surface area e g WAGO shield connecting system This is especially recommended for large scale systems where equalizing current or high impulse type...

Страница 23: ...4 4 4 WAGO Shield Connecting System The WAGO shield connecting system consists of shield clamping saddles busbars and various mounting carriers to enable a wide variety of setups For more information...

Страница 24: ...inputs Figure 5 Terminal assignment for digital inputs Connection Short name Designation 5 DI1 Digital input 1 6 DI2 Digital input 2 7 DI3 Digital input 3 8 DI4 Digital input 4 9 DI5 Digital input 5...

Страница 25: ...unter inputs Table 7 Counter input pin assignments Figure 6 Counter input pin assignments Connection Short name Explanation 5 DI1 Counter input 1 configurable 6 DI2 Counter input 2 configurable 7 DI3...

Страница 26: ...inputs Figure 7 Terminal assignment for analog inputs Connection Short name Designation 13 AI1 Analog input 1 14 AI1 Analog input 1 15 AI2 Analog input 2 16 AI2 Analog input 2 17 AI3 Analog input 3 1...

Страница 27: ...on 1 0 0 Analog inputs are single ended The analog inputs are single ended and the Aix connections are connected internally to the GND connections Connect shielding Shielded cables are required for an...

Страница 28: ...V PELV voltages Only SELV PELV voltages shall be connected to the device terminals Table 9 Terminal assignment for digital outputs Figure 8 Terminal assignment for digital outputs Connection Short nam...

Страница 29: ...terminals Table 10 Terminal assignment for analog outputs Figure 9 Terminal assignment for analog outputs Connection Short name Designation 29 AO1 Analog output 1 30 AO1 Analog output 1 31 AO2 Analog...

Страница 30: ...PC and MODBUS interface Pin Description 1 Not assigned 2 TXD 3 RXD 4 Not assigned 5 GND 6 Not assigned 7 MODBUS D1 B 8 MODBUS D0 A 9 Not assigned Table 12 PC interface cable assignment TO PASS Telecon...

Страница 31: ...quires a line terminator at both ends of an RS 485 bus If the TO PASS telecontrol module is operated at one end of the line the terminator must be added e g directly in the D Sub plug in connector or...

Страница 32: ...761 761 217 Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 Connect shielding Shielded cables are required for MODBUS communication The cable shield must be connected to the DIN rai...

Страница 33: ...M modem is activated Initialization takes approx 40 s after system start up if everything is OK SMS GPRS processing Antenna is not connected the modem is searching for a network Poor GSM network the m...

Страница 34: ...22 AWG 14 sol Stripped length 9 mm 10 mm 3 6 2 Supply Table 16 Technical Data Supply Operating voltage 10 V 30 VDC Nominal voltage operation with mains power 24 VDC Nominal voltage operation using bat...

Страница 35: ...ry Input Holding Interface speed 9600 Baud 19200 Baud Interface parameters 8N2 8E1 8O1 8N1 Bias network permanently integrated 2 x 470 0 25 W at GND and 5 V Line terminator not integrated See informat...

Страница 36: ...uts 4 Output type Semiconductor outputs Output current 0 5 A 30 V DC short circuit protected Type of load Resistive inductive lamps Energy dissipation Wmax unique switching off 125 mJ Lmax 2 Wmax I2 3...

Страница 37: ...TTE Complaint with 1999 5 EG directive per Article 3 2 RoHS Device complies with European RoHS directive FCC Verification per FCC 15b 3 8 Standards and Guidelines 761 217 telecontrol modules meet the...

Страница 38: ...for an ambient temperature of 20 C to 70 C In the event of higher or lower temperatures proper cooling or heating arrangements must be provided Please contact WAGO Kontakttechnik GmbH Co K G for assi...

Страница 39: ...Removing the TO PASS telecontrol module from the DIN rail Figure 14 Removing the TO PASS telecontrol module from the DIN rail 1 Press the undersurface against the lower DIN rail edge until the TO PAS...

Страница 40: ...to one connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals Terminate both solid and ferruled conductors without actuation by simply pushi...

Страница 41: ...e DIN rail The shield connection of the TO PASS telecontrol module shield terminal 38 must be connected to the DIN rail The DIN rail must have a low impedance ground see section Connections Ground 5 2...

Страница 42: ...ct SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are recommended for the counter inputs When using shielded cables the shield...

Страница 43: ...vice terminals Analog inputs are single ended The analog inputs are single ended and the Aix connections are connected internally to the GND connections Connect shielding Shielded cables are required...

Страница 44: ...former Voltage measurement cannot be performed via multiplier at the analog inputs since the internal resistance of the TO PASS telecontrol module depends on the input current WAGO 857 Series JUMPFLEX...

Страница 45: ...Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 5 2 4 Digital Outputs Only connect SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Figure 19 C...

Страница 46: ...ect SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are required for analog outputs The cable shield must be connected to the gr...

Страница 47: ...61 217 Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 5 2 5 2 Voltage Measurement RL Load resistance RM Internal resistance of measuring device RL RM must be less than 600 With RM...

Страница 48: ...0 resistor 0 5 W or a 1nF capacitor at least 10 V and a 120 resistor 0 25 W connected in series can be used for this If the TO PASS telecontrol module is operated outside the bus not at the end the br...

Страница 49: ...ASS 761 Connect Devices 49 761 217 Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 5 2 6 1 MODBUS Coupler Controller RS 485 Figure 21 Connection example for MODBUS Coupler Controlle...

Страница 50: ...PASS 761 761 217 Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 5 2 6 2 Serial Interface for MODBUS Current Sensor and PC Figure 22 Connection example for serial interface for MOD...

Страница 51: ...Explorer using a double click 5 Select the CD drive in which you have placed the CD with the operating software 6 Start the WAGO TO PASS_SETUP 2 17 EXE program or a newer version in the main directory...

Страница 52: ...g the TO PASS telecontrol module it must first be configured with the telephone number 1 Every TO PASS telecontrol module requires an SIM card for proper operation You can obtain an SIM card from any...

Страница 53: ...he Use PIN button so that the TO PASS telecontrol module does not use the PIN code Also deactivate the PIN on the SIM card To do this insert the SIM card into a cell phone and under menu item Security...

Страница 54: ...M Analog ISDN Select the type of connection for communicating with the TO PASS telecontrol module RS 232 Direct connection via RS 232 cable GSM Dial up using GSM modem on the PC Analog Dial up using a...

Страница 55: ...erface COM1 COMx Here select the serial interface where the communication cable is connected with a RS 232 connection Language English German French Select the langauge for the TO PASS operator interf...

Страница 56: ...ter you have set the type of connection for communicating with the TO PASS telecontrol module you are then able to read out the parameters of the connected module Select the menu option Edit Read Para...

Страница 57: ...odule to be configured from the project tree under it select the Identity option On the right side you will find the selection field for the function the display field for the name the input field for...

Страница 58: ...button and enter the PIN number in the field provided Roaming Roaming is always activated in TO PASS telecontrol modules To select a favorite carrier click the Allow button and enter the 5 digit carri...

Страница 59: ...Messages are sent by the TO PASS telecontrol module as SMS however they can also be sent as an e mail fax or voice mail as defined in configuration The TO PASS telecontrol module can also transmit me...

Страница 60: ...e e mail address e g for a T Mobile SIM card 8000 receiver provider net Transmission as fax Follow the instructions from the provider for transmissions as fax messages For T Mobile or Vodafone for exa...

Страница 61: ...ogger for transmitting the data of the logger APN access In this field enter the APN access point Access Point Name for the SIM card provider e g T Mobile internet t mobile Vodafone web vodafone de Th...

Страница 62: ...Digital Inputs Digital inputs 1 4 can be configured as counter inputs starting from Firmware Version FW 2 33 The counters count up or down from the given starting and end value With upward counting ex...

Страница 63: ...tion via the visualization system This function is available starting with Firmware Version FW 2 33 Starting value In this field enter the starting value for the counter This field is only active when...

Страница 64: ...t for applications with GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the message when the digital input has been set or when t...

Страница 65: ...tions with GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the deactivation message when the digital input has been reset or when...

Страница 66: ...The following applies in this case DI1 20 1 DI2 21 2 DI3 22 4 and DI4 23 8 Thus for example if DI1 and DI3 are set then the binary number is 5 If only DI4 is set then the binary number is 8 In the mu...

Страница 67: ...ttings Enable Addresses Multiplex operation Click the button Use to enable disable multiplex operation for digital inputs DI1 DI4 If a status combination of digital inputs DI1 DI4 is fulfilled in mult...

Страница 68: ...er the Multiplex Input entry The input fields for the alarm texts pertaining to the 16 statuses are provided on the right side Figure 29 Configuring multiplex operation alarm texts Table 31 Configurin...

Страница 69: ...the analog inputs Table 32 Configuring the analog inputs Standardization Input signal Use these buttons to select the input signal for the sensor connected to the TO PASS telecontrol module Min value...

Страница 70: ...alog value Use these buttons to select up to four analog values which can also be transmitted with the message when the analog value has violated the first upper lower limit Second value In this field...

Страница 71: ...and connects the DC voltage available at terminal 37 to the corresponding output Deactivation text In this field enter the deactivation text for the output When the TO PASS telecontrol module receives...

Страница 72: ...ect the output signal for the actuator connected to the TO PASS telecontrol module Min value In this field enter the starting value from which the output value is normalized This value corresponds to...

Страница 73: ...aces after the decimal point are also taken into account for switching of the analog outputs A period decimal point must be used as the separator Up to four digits are evaluated With a minimum value o...

Страница 74: ...ates of digital inputs are to be sent as error messages select the desired recipient for the respective input statuses using buttons 1 4 Click the Internet button to also transmit the message to a Web...

Страница 75: ...lecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 4 Click the Internet button to also transmit the message to a Web portal In addition you can also specify the analog values that are to...

Страница 76: ...O PASS telecontrol module waits for an acknowledgement after transmitting an alarm SMS Acknowledgement is in the form of an SMS containing the configured response text or a simple call by the recipien...

Страница 77: ...s Select the TO PASS telecontrol module from the project tree using the identifier Select the entry Repeat times under the option Special Functions The input fields for the Web interval the Web output...

Страница 78: ...al This function is available starting with Firmware Version FW 2 33 Switching input In this field select a digital input to be used for switching of the transmission interval between Web interval Off...

Страница 79: ...ertain times of day Time adjustment must be performed for limited SMS transmission to check the day of the week and the active time The first SMS is transmitted when the starting value for the active...

Страница 80: ...djustment Table 37 Setting the time adjustment Settings Time adjustment The TO PASS telecontrol module sends an SMS to itself and receives the current time from the provider transmitted by this SMS wh...

Страница 81: ...on 1 0 0 7 9 MODBUS The MODBUS functionality facilitates connectivity for MODBUS interface equipped devices The devices must be configured as slave devices and are connected via PC interface As a resu...

Страница 82: ...roller used The following formats are possible Not used no MODBUS connection 9600 8N2 RTU Input 0x04 9600 8E1 RTU Input 0x04 9600 8O1 RTU Input 0x04 9600 8N1 RTU Input 0x04 9600 8N2 RTU Holding 0x03 9...

Страница 83: ...ODBUS alarm under the MODBUS entry The input fields and buttons for the alarms are provided on the right side Figure 37 Configuring the MODBUS alarm Table 39 Configuring the MODBUS alarm Alarm Setting...

Страница 84: ...DBUS entry The input fields for the addresses of the registers to be polled are provided on the right side The input fields are identical for all register groups Figure 38 Configuring the MODBUS regis...

Страница 85: ...d enter the cycle time in minutes at which the process image is to be saved The process image is specific to devices and firmware used and is described in the Section Operation Data Logger DSP The dat...

Страница 86: ...fter you have adapted all parameters for the TO PASS telecontrol module to your requirements you have to write the parameters to the connected module Select the menu option Edit Write Parameters The s...

Страница 87: ...ule Compact 8 AI Web MODBUS485 Manual Version 1 0 0 8 Operation 8 1 Remote Query of Process Values The TO PASS telecontrol module offers two options for remote inquiry of the process values available...

Страница 88: ...1 4 0 not set 1 set 00 00mA Analog output 1 00 00mA Analog output 2 Normal Status Status text or prepaid information optional AC 99 Alarm counter displays the alarms that are still possible per hour T...

Страница 89: ...ses Table 44 Counter status Status Explanation 0 Digital input not configured as a counter e ZW Counter is active Counter value d ZW Counter is not active Counter value o ZW Counter overflow Counter v...

Страница 90: ...cess values with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mode used to...

Страница 91: ...the on line display is green Figure 40 Visualization of the process values Process values pertaining to inputs are displayed in the upper portion of the window and those pertaining to digital and ana...

Страница 92: ...values The process values displayed are valid if the on line display is green Figure 41 MODBUS process values MODBUS Alarm In this line the variable for the MODBUS alarm Module Register Text is displa...

Страница 93: ...es click the Counter button possible only when inputs have been configured as counters The process values displayed are valid when the on line indicator is highlighted in green Figure 42 Counter proce...

Страница 94: ...MODBUS485 Manual Version 1 0 0 8 2 Telecontrol TO PASS telecontrol modules offer the option of influencing a process remotely with the help of their analog and digital outputs There are two methods av...

Страница 95: ...an SMS containing the identifier and the transmitted text Example Table 45 Example of parameters for Set DO Parameter Setting Activation text DOUT1 1 Deactivation text DOUT1 0 Turn off time 00 00 00...

Страница 96: ...t AO1 Parameter Setting Output Signal 0 20 mA Min value 0 Max value 100 Unit Text AOUT1 Send an SMS with the text AOUT1 75 to set analog output 1 to a value of 15 mA 75 The TO PASS telecontrol module...

Страница 97: ...l commands for counters Control command Function Cx x 1 4 Select counter 1 4 E Activate counter D Deactivate counter R Reset counter n e g 500 Set counter value Control commands must be concluded with...

Страница 98: ...s values with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mode used to dia...

Страница 99: ...inputs are displayed in the upper portion of the window and those pertaining to digital and analog outputs are displayed in the lower portion of the window Digital inputs configured as counter inputs...

Страница 100: ...lighted in green Figure 44 Counter process values The counter statuses are shown at the top of the window while the counter values the starting and end values and the limits are shown at the bottom To...

Страница 101: ...acknowledgement SMS containing the identifier the response text and the alarm text Acknowledgement by phone call is based on the card being used Some data cards do not allow voice links meaning that a...

Страница 102: ...ifically to the respective ready state This takes place with simple changeover via SMS To do this just send an SMS with the text Standby1 to the TO PASS telecontrol modules The TO PASS telecontrol mod...

Страница 103: ...values of the data logger using the menu item Visualization Data logger Either select all inputs or only specific inputs with the help of the selection field in the upper portion of the window All ent...

Страница 104: ...Web MODBUS485 Manual Version 1 0 0 As an alternative you can also display all data records saved via Edit Display all data records or all new data records for the selected telecontrol module via Edit...

Страница 105: ...saved To read the contents of the event logger select the menu option Edit Read all data records It is possible to display all values of the event logger with the help of the menu option Visualization...

Страница 106: ...f the outputs are displayed in the lower area By pressing the buttons Output 1 Output 4 in the upper area switch digital inputs on and off A value range of 0 mA 20 mA and 4 mA 20 mA is defined for the...

Страница 107: ...ng and end values and the limits are shown at the bottom To start a counter click the button Activate To stop a counter click the button Deactivate To restore the counter to its starting value click t...

Страница 108: ...with a direct serial link to the TO PASS telecontrol module To test the connection select the menu option Edit Test SMS GPRS The following window is displayed Figure 47 Testing the connection Select...

Страница 109: ...ial link required The modem test may only be performed with a direct serial link to the TO PASS telecontrol module To test the mode select the menu item Modem Test The following window is displayed Fi...

Страница 110: ...IM card provider for APN access user name and password see also Section Parameter setting Addresses Under Special Functions select Repetition Time and set the WEB Interval for the cyclic transmission...

Страница 111: ...ted by the character 10 2 1 Example HTTP Request The HTTP request consists of both header and data string which are separated by an empty line CR LF Carriage Return Line Feed To improve readability li...

Страница 112: ...inor extensions In the data set descriptions the maximum number of characters is indicated in square brackets Starting from Firmware Version 02 33 08 you can select the script version to be applied to...

Страница 113: ...1 11 A1 Analog input 1 Value 6 Unit 5 Alarm 1 12 A2 Analog input 2 Value 6 Unit 5 Alarm 1 13 A3 Analog input 3 Value 6 Unit 5 Alarm 1 14 A4 Analog input 4 Value 6 Unit 5 Alarm 1 15 A5 Analog input 5 V...

Страница 114: ...ard To improve readability line breaks have been inserted ID TO PASS 12345 PA 0000 home 99 TI 11 05 05 14 34 21 D1 1 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 0...

Страница 115: ...lue 1 Alarm 1 11 D8 Digital input 8 Value 1 Alarm 1 12 A1 Analog input 1 Value 6 Unit 5 Alarm 1 13 A2 Analog input 2 Value 6 Unit 5 Alarm 1 14 A3 Analog input 3 Value 6 Unit 5 Alarm 1 15 A4 Analog inp...

Страница 116: ...eviation is not enabled 1 Position deviation is enabled Flag 3 0 GPS receiver is turned off 1 GPS receiver is turned on Flag 4 0 No valid position available 1 Valid position available Flag 5 0 Static...

Страница 117: ...ave been inserted ID TO PASS Ext 12345 SV 01 01 PA 0000 home 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5...

Страница 118: ...DO 0000 AO 000 0 04 00 mA C1 0 0 0 C2 r 20F5800 0 C3 r 0 0 C4 0 0 0 SQ 21 US Hello MA 00 00 0 MV 0026 0000 002E 0064 0026 0000 0054 0064 HT 1 value always 1 the device time has not been set TI entry...

Страница 119: ...1 First value reached transgressed 2 Second value reached transgressed If both values are reached simultaneously only status 2 is transmitted SQ Signal quality or modem connection without formatting...

Страница 120: ...0000 home 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5 00 00 mA 0 A6 00 00 mA 0 A7 00 00 mA 0 A8 00 00 mA...

Страница 121: ...e Compact 8 AI Web MODBUS485 Manual Version 1 0 0 10 3 2 Logger Script Data transmission to the logger script is activated via cyclical transmission repetitions Web interval Data packet information co...

Страница 122: ...Data Set Byte 0 1 2 3 4 5 6 Bit 76543210765432107654321076543210765432107654321076543210 Cont PNNNNNNNSJJJJJMMMMDDDDDhhhhhmmmmmmssssssDIN AIN1 Byte 7 8 9 10 11 12 13 Bit 765432107654321076543210765432...

Страница 123: ...y line breaks have been inserted ID TO PASS 12345 PA 0005 home 99 TI 11 05 05 14 36 11 LO 092D4AD100000000000000000000 562D4AD123000000000000000000 3F2D4AD12A000000000000000000 562D4AD1370000000000000...

Страница 124: ...7 LPD2 2 GPS message 81 see LPDx variable data format table 8 LIO3 3 I O message 74 see LIOx variable data format table 9 LPD3 3 GPS message 81 see LPDx variable data format table 10 LIO4 4 I O messa...

Страница 125: ...input Value 3 10 7 analog input Value 3 11 8 analog input Value 3 12 Supply voltage Value 3 13 Digital output image Image 1 14 1 analog output Value 3 15 2 analog output Value 3 10 3 2 2 2 Data Forma...

Страница 126: ...000 000 000 000 000 000 B89 0 000 000 LPD3 C0 11 05 05 06 34 25 276 C41 2600 N 216 1621 E 0C 4D34 3 26A F 21 11 7 0 LIO4 001C 56 11 05 05 08 34 36 00 000 000 000 000 000 000 000 000 B83 0 000 000 LPD4...

Страница 127: ...44 0x2C 2C Altitude in m 51 5 51 5 10 515 0x203 203 Position accuracy 2 2 Direction 309 35 309 x 60 35 18575 0x488F 488F Speed in km h 3 7 3 7 10 37 0x25 25 Speed in knots 2 0 2 0 10 20 0x14 14 Numbe...

Страница 128: ...lue 2nd input hexadecimal Value 8 4 Counter status 3rd input Status 1 5 Counter value 3rd input hexadecimal Value 8 6 Counter status 4th input Status 1 7 Counter value 4th input hexadecimal Value 8 Th...

Страница 129: ...0 09 16 00 003 32E 7D5 7D9 7DA 7D8 7D6 7D5 AD0 0 000 32D LCD1 0 0 r 54600 r 0 0 0 LIO2 0001 11 00 01 01 00 09 52 00 CE3 32E 7D5 7D8 7DA 7D7 7D6 7D4 ACE 0 D04 32D LCD2 0 0 e 54600 d 0 0 0 LIO3 0002 78...

Страница 130: ...al Version 1 0 0 10 3 2 4 Time Request Script FW 2 33 If time adjustment is to take place via the Internet a time request script is transmitted on system start in order to adjust the time when a reply...

Страница 131: ...02 33 08 setpoint settings for digital and analog outputs and for changing the counters can be transmitted as replies Table 62 Setpoint settings Variable Contents Format AO1 1 analog output Normalize...

Страница 132: ...rver Apache CR LF Content length 31 CR LF Keep alive timeout 15 max 100 CR LF Connection Keep Alive CR LF Content type text html CR LF CR LF Values stored 08 09 19 13 22 23 The header depends on both...

Страница 133: ...nnection example for a relay at DO1 output 45 Figure 20 Connection example for a display device at AO1 output 46 Figure 21 Connection example for MODBUS Coupler Controller RS 485 49 Figure 22 Connecti...

Страница 134: ...134 List of Figures WAGO TO PASS 761 761 217 Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0 Figure 47 Testing the connection 108 Figure 48 Testing the modem 109...

Страница 135: ...1 Technical Data Counter Inputs 35 Table 22 Technical Data Analog Inputs 36 Table 23 Technical Data Digital Outputs 36 Table 24 Technical Data Analog Outputs 36 Table 25 Technical Data Data and event...

Страница 136: ...rm status 119 Table 54 Signal quality from AT Reference Guide by Telit 119 Table 55 Data format for logger script FW 2 20 standard 122 Table 56 Data format for logger script FW 2 31 extended 124 Table...

Страница 137: ...WAGO TO PASS 761 137 761 217 Telecontrol Module Compact 8 AI Web MODBUS485 Manual Version 1 0 0...

Страница 138: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Отзывы: