124 WAGO TO-PASS® Web
WAGO-TO-PASS® 761
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
Manual
Version 1.0.0
10.3.2.2 Logger Script Extension
The logger script has been updated due to extended functionalities. The “02.00”
version designation has been assigned due to major modifications.
Table 56: Data format for logger script FW 2.31 (extended)
Index
Variable
Contents
Format
0
ID
Identity
Identity[8];Serial number[5]
1
LV
Logger script version
Version number[5] (currently “02.00”)
2
PA
Parameter
Cycle time[4];Provider[5];Alarm counter[2]
3
TI
Date, time
YY/MM/DD,hh:mm:ss;
4
LIO1
1. I/O message
[74] (see LIOx variable data format table)
5*
LPD1
1. GPS message
[81] (see LPDx variable data format table)
6
LIO2
2. I/O message
[74] (see LIOx variable data format table)
7*
LPD2
2. GPS message
[81] (see LPDx variable data format table)
8
LIO3
3. I/O message
[74] (see LIOx variable data format table)
9*
LPD3
3. GPS message
[81] (see LPDx variable data format table)
10
LIO4
4. I/O message
[74] (see LIOx variable data format table)
11*
LPD4
4. GPS message
[81] (see LPDx variable data format table)
12
LIO5
5. I/O message
[74] (see LIOx variable data format table)
13*
LPD5
5. GPS message
[81] (see LPDx variable data format table)
14**
LIO6
6. I/O message
[74] (see LIOx variable data format table)
15**
LIO7
7. I/O message
[74] (see LIOx variable data format table)
16**
LIO8
8. I/O message
[74] (see LIOx variable data format table)
17**
LIO9
9. I/O message
[74] (see LIOx variable data format table)
* This variable is sent only if the GPS functionality is available in the
TO-PASS
®
telecontrol module.
** This variable is not sent if the GPS functionality is available in the
TO-PASS
®
telecontrol module.
The meaning of the LIOx and LPDx variables are given in the following tables: