WAGO-TO-PASS® 761
Parameterizing
71
761-217 Telecontrol Module Compact, 8 AI, Web, MODBUS485
Manual
Version 1.0.0
7.5.4
Digital Outputs
Select your
TO-PASS
®
telecontrol module from the left side of the project tree
using the identifier. Select the output to be configured under the entry
Digital
Outputs
.
The parameters of the output are given on the right side. The input fields are
identical for all digital outputs:
Figure 31: Configuring the digital outputs
Table 33: Configuring the digital outputs
Settings
Activation text
In this field enter the activation text for the output.
When the
TO-PASS
®
telecontrol module receives this text as
an SMS it switches this digital input on and connects the DC
voltage available at terminal 37 to the corresponding output.
Deactivation text
In this field enter the deactivation text for the output.
When the
TO-PASS
®
telecontrol module receives this text as
an SMS it deactivates this digital output and disconnects the
DC voltage available at terminal 37.
Turn-off time
In these fields select the turn-off time for the output in hours,
minutes and seconds.
If the digital output has been activated, it will remain active
for the time defined here and voltage remains applied at
terminal 37. When this time elapses, the output switches off
the voltage at terminal 37 automatically.
The maximum turn-off time is limited to "00:01:59" up to
Firmware Version FW 2.33.
Define a time of "00:00:00" hh:mm:ss to deactivate this
function. The output will then remain permanently activated
until the next deactivation message is received.