82 Commissioning
WAGO I/O System 750
753-482 2AI 4-20mA 12 Bit S.E. HART
Manual
Version 1.2.0
Figure 44: Dialog Window DTM Parameters
16. Select the desired module from the left side of the tree structure; the
displayed module number corresponds to the slot in the structure – module
01 is the bus coupler.
The right side contains the parameterization dialog for this module.
17. Set the desired parameter for each channel separately, such as
• the analog
Filter time
for the input channel (10 ms ... 640 ms),
• the
Simulation
mode activation, and
• the
Simulation value
setting with the
Over range
or
Under range
selection.
When the simulation is activated, the selected simulation value is output as
a process value. When selecting an overflow or underflow, the overflow or
underflow is overlaid (last 2 bits), as output in the status byte.