70 Commissioning
WAGO I/O System 750
753-482 2AI 4-20mA 12 Bit S.E. HART
Manual
Version 1.2.0
A Boot-Project for HART functionality is necessary!
In order to be able to use the HART functionality, a special boot project for
Ethernet controllers must be loaded into the ETHERNET Controller 750-841. You
can download this boot project and more detailed information relating to it on the
WAGO website at:
www.wago.com
→ Support → Additional documentation and information on
automation products → Application Notes
, under the number: “
A116101
”.
6.
Now move the operating mode switch on your ETHERNET controller, which
is to be found on the programming and configuration interface, into the
upper position.
7.
Open the
WAGOframe
in “Expert mode”.
8.
Next make sure that the “Device catalog” dialog window is shown on the
right-hand side of the screen. This must be activated under
Device catalog
on the
View
menu.
Click on
[Update]
in the “Device catalog” dialog window.
9.
Open a new project using
New
on the
File
menu.
10. Make sure that the “Network view” dialog window is shown on the left-hand
side of the screen. This must be activated under “Network view” on the
View
menu.
Move the mouse to “Network” in the tree structure and click on
Add...
in the
context menu (right mouse button).
Select “WAGO Modbus TCP” in the dialog which opens and confirm the
selection by clicking
[OK].
The entry “MODBUS TCP_DTM*” will now be added to the tree structure.
11. Click
Set up connection
on the
Device
menu. The entry “MODBUS
TCP_DTM*” will now be changed to italics in the tree structure.
12. Move the mouse to “
MODBUS TCP_DTM
” in the tree structure and click on
[Add....]
in the context menu (right mouse button).
Select “075x-08xx ModbusTCP/HART Gateway” in the dialog which opens
and confirm the selection by clicking
[OK].
The entry “<ModbusCommChannel:-> 075x-08xx DTM*” will now be added
to the tree structure.
13. Now move the mouse once again to “
MODBUS TCP_DTM
” in the tree
structure and select it by clicking with the left mouse button.
Next go to “More functions” on the
Device
menu and click on
Device list
on the sub-menu.
A dialog window with a list of devices will open.
Select the device with the address “0.0.0.0” by clicking on it and click
Change DTM tag/address....
In the new view now enter the “IP address” of your ETHERNET controller in
place of the “0.0.0.0”.
Confirm your entry by clicking
[OK].
The IP address which you have entered will now be displayed in the list in
the “ModbusTCP_DTM device list” dialog window.
Next click on
Check devices.
If all parameters are correctly set, the status of the DTM will now be shown
in green.