52 Operating Modes
WAGO I/O System 750
753-482 2AI 4-20mA 12 Bit S.E. HART
Manual
Version 1.2.0
8
Operating Modes
The HART I/O module can be used with various operating modes depending on
connection and parameterization.
Table 29: Overview of Operating Modes
Operating Mode
On Fieldbus
Coupler/Controller
Use
2 AI + 6 bytes mailbox
(Default)
All compatible Fieldbus
couplers/controllers
75x-xxx
*)
1) With
“WagoLibHART_0x.lib”
PLC library
750-841
ETHERNET TCP/IP
Fieldbus controller
2) With ModbusTCP/HART
Gateway 759-359
2 AI + 1 HART variable
per Channel
PROFIBUS DP/V1
Fieldbus coupler
750-333 or Fieldbus
controller 750-833
3) With HART dynamic
variables
2 AI + 2 HART variables
per Channel
2 AI + 3 HART variables
per Channel
2 AI + 4 HART variables
per Channel
2 AI + acyclic PROFIBUS
services
4) With PROFIBUS/HART
Gateway 759-360
*)
see table “Compatibility List”
In the as-supplied state, the HART I/O module is configured in the default
operating mode as a 2-channel analog input module for 4 mA … 20 mA signals
with HART functionality. In this default operating mode the I/O module can be
connected to all WAGO couplers and controllers listed in the table “Compatibility
List”. In this case, HART communication is enabled by a 6-byte mailbox, which is
incorporated with the analog values in the cyclic process image.
In addition, five further operating modes can be set up specially for connecting to
the PROFIBUS DP/V1 Fieldbus Coupler 750-333 or Fieldbus Controller 750-833.
The section “Description of Operation” following the section on parameterization
and a short introduction to the FDT/DTM concept and HART via PROFIBUS,
describes the individual operating modes in the appropriate applications in more
detail together with a description of the communications process and brief
commissioning instructions in each case.
8.1
Setting the Operating Mode Parameters
Depending on the fieldbus used, the HART I/O module can either be
parameterized using the “759-302 WAGO-I/O-
CHECK
” commissioning tool for
WAGO-I/O-SYSTEM 750 or, for PROFIBUS, using the GSD files (device master
data) for PROFIBUS with installation program / Series 750, 752 and 755 (Item
No.: 750-910).