5.5
Collections of Measured Values
5.5.1
Collection 007 – DC Measured Values
Wait to the end of build-up time!
The selected measured values of the collection are stable after approx. 1400 ms!
Table 17: Measured Values of Collection 007 in the Process Image (PI)
MET_ID Measured Value
Data
Type
PI
Scaling Factor PI
Update
Rate PI
[ms]
1A-
Variants
5A-
Variants
Current
001
DC current L1
UInt32
0.0001A
0.0005A
40
002
DC current L2
UInt32
0.0001A
0.0005A
40
003
DC current L3
UInt32
0.0001A
0.0005A
40
Voltage
004
DC voltage L1-N
UInt32
0.01V
0.01V
40
005
DC voltage L2-N
UInt32
0.01V
0.01V
40
006
DC voltage L3-N
UInt32
0.01V
0.01V
40
Power
007
Power (DC current) L1
UInt32
0.01W
0.05W
40
008
Power (DC current) L2
UInt32
0.01W
0.05W
40
009
Power (DC current) L3
UInt32
0.01W
0.05W
40
5.5.2
Collection 009 – AC Measured Values
Wait to the end of build-up time!
The selected measured values of the collection are stable after approx. 1400 ms!