WAGO-I/O-SYSTEM 750
Appendix 115
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
Table 58: Parameter 22
Parameter 22 – Storing interval for energy values
Function
Data type
Access
Factory setting
-Corresponds to register 46. (See section above.)
Table 59: Parameter 23
Parameter 23 – Overvoltage threshold phase L1
Function
Data type
Access
Factory setting
Overvoltage threshold phase L1,
Resolution: 0.1 V
UINT
R/W
0x09C4 (250 V)
Table 60: Parameter 24
Parameter 24 – Overvoltage threshold phase L2
Function
Data type
Access
Factory setting
Overvoltage threshold phase L2,
Resolution: 0.1 V
UINT
R/W
0x09C4 (250 V)
Table 61: Parameter 25
Parameter 25 – Overvoltage threshold phase L3
Function
Data type
Access
Factory setting
Overvoltage threshold phase L3,
Resolution: 0.1 V
UINT
R/W
0x09C4 (250 V)
Table 62: Parameter 26 and 27
Parameter 26 und 27 – Overcurrent threshold phase L1
Function
Data type
Access
Factory setting
Overcurrent threshold phase L1,
Resolution: 0.1 mA
UINT
R/W
0x02FAF080
(5 000 A)
0:
Overcurrent is not checked.
≥1
:
Overcurrent threshold (value)
Table 63: Parameter 28 and 29
Parameter 28 und 29 – Overcurrent threshold phase L2
Function
Data type
Access
Factory setting
Overcurrent threshold phase L2,
Resolution: 0.1 mA
UINT
R/W
0x02FAF080
(5 000 A)
0:
Overcurrent is not checked.
≥1
:
Overcurrent threshold (value)