WAGO-I/O-SYSTEM 750
Process Image
45
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
STAT4
STAT_SEL = Status Lx = L1 / L2 / L3:
- Status Zero crossings:
0 = Signal zero crossings at the phase Lx
1 = No signal zero crossings at the phase Lx
STAT_SEL = Status I/O module:
No significance
STAT3
STAT_SEL = Status Lx = L1 / L2 / L3:
- Clipping of voltage signal at Lx:
0 = OK
1 = The voltage signal is outside the measurable
range of the I/O module and has been
limited (clipped).
STAT_SEL = Status I/O module:
No significance
STAT2
STAT_SEL = Status Lx = L1 / L2 / L3:
- Clipping of current signal at Lx:
0 = OK
1 = The current signal is outside the measurable
range of the I/O module and has been
limited (clipped).
STAT_SEL = Status I/O module:
No significance
STAT1
STAT_SEL = Status Lx = L1 / L2 / L3:
- SagLevel Voltage Lx:
0 = OK
1 = Elevated measuring error due to inadequate
input voltage at Lx
STAT_SEL = Status I/O module:
No significance
Byte 3
(Bit 7) (Bit 6)
(Bit 5)
(Bit 4)
(Bit 3)
(Bit 2)
(Bit 1)
(Bit 0)
COL_ID_SEL
COL_ID_SEL
Index for the selected measured value collection (see also
COL_ID in output data):
000 … 006= reserved
007 = DC measured values
008 = reserved
009 = AC measured values
010 … 019= reserved
020 = Harmonics analysis L1
021 = Harmonics analysis L2
022 = Harmonics analysis L3
023 … 255= reserved