Function Description
Pos: 74 /Serie 750 ( WAGO-I/O-SYST EM)/F unktionsbeschr eibung/Funkti onsbeschrei bung 750-0494 - Messprinzip, Messwerte @ 14\mod_1363085168365_21.docx @ 114260 @ 222 @ 1
4.1
Measuring Principle
The 3-phase power measurement module operates using 6 analog/digital
converters for acquiring the current and voltage levels in all three phases.
The 3 phases are connected to the current measuring channels of the I/O module
in "single-ended" measurement topology, i.e. all secondary windings of the
current transformers are connected to the common clamp IN. Low pass filters on
the 6 measuring inputs have a limit frequency of 15.9 kHz. Each input signal is
scanned at a frequency of 8 kHz, quantized with 24 bits and further processed
digitally.
Acquisition and processing of the measured values of all three phases is
performed
simultaneously in the very same way
.
4.2
Measured Values
The 3-phase power measurement module makes the following
AC measured
values
available per phase (Lx, Ly = L1, L2 or L3):
Voltage:
• RMS value voltage
Lx-N
• Max
. RMS value voltage Lx-N
• Min
. RMS value voltage Lx-N
• Arithmetic mean value voltage
Lx-N
• Peak value voltage
Lx-N
• RMS value phase
-to-phase voltage Lx-Ly
Current:
• RMS value current Lx
• Max
. RMS value current Lx
• Min
. RMS value current Lx
• Arithmetic mean value current Lx
• Peak value current Lx
Power:
• Active power Lx
• Max
. active power Lx
• Min
. active power Lx
• Reactive power Lx
• Apparent power Lx
Energy:
• Active
energy Lx
• Active energy acquisition Lx
• Active energy delivery Lx
• Active energy total