WAGO-I/O-SYSTEM 750
Appendix 107
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0
Pos: 110 /Serie 750 (WAGO-I/O-SYST EM)/In Betri eb nehmen/Par ametrieren über R egister kommuni kati on/Registerbeleg ung und Parameterbel. 750-494 @ 15\mod_1364991593084_21.docx @ 116384 @ 22 @ 1
10.3 Register Assignment
The tables below show the assignments and factory settings for the registers
written during configuration and during operation. All registers have a size of two
bytes.
Table 24: Register 4
Register 4 – Command interface request
Function
Data type
Access
Factory setting
Command Interface Request
UINT
R/W
0x0000
High byte
Sequence number (Session ID)
Low byte
Request
0x04
Reset register and calibration data to factory default settings
0x37
Preset apparent energy delivery phase L1
0x38
Preset apparent energy delivery phase L2
0x39
Preset apparent energy delivery phase L3
0x3A
Preset active energy acquisition phase L1
0x3B
Preset active energy delivery phase 1
0x3C
Preset active energy acquisition phase L2
0x3D
Preset active energy delivery phase L2
0x3E
Preset active energy acquisition phase L3
0x3F
Preset active energy delivery phase L3
0x40
Preset reactive energy inductive phase L1
0x41
Preset reactive energy capacitive phase L1
0x42
Preset reactive energy inductive phase L2
0x43
Preset reactive energy capacitive phase L2
0x44
Preset reactive energy inductive phase L3
0x45
Preset reactive energy capacitive phase L3
0x91
Save energy consumption early
0x92
Delete all minimum and maximum values
0x93
Delete minimum RMS current
0x94
Delete maximum RMS current
0x95
Delete minimum RMS voltage
0x96
Delete maximum RMS voltage
0x97
Delete minimum power
0x98
Delete maximum power
0x99
Initialize all energy meters to 0
0x9A
Delete minimum frequency
0x9B
Delete maximum frequency
0x9C
Reset registers and parameters to factory settings
0x9D
Reset calibration data to factory settings
0xA0
Start mode for manufacturer calibration for AC operation
0xA1
Start mode for manufacturer calibration for DC operation
0xA2
Start mode for user calibration for AC operation
0xA3
Start mode for user calibration for DC operation
0xA4
Start mode for measuring operation (halts calibration mode)