4.3.13 Resistance Measurement 1, 0 Ohm … 5.0 kOhm, ID 14
No short-circuit detection for resistance measurements!
For sensor types “Resistance measurement 1” and “Resistance measurement 2”,
short-circuit detection is not technically possible.
4.3.13.1 Default Format
With the setting “Resistance measurement 1" (0 Ohm to 5.0 kOhm), the I/O
module outputs the measured resistance values of the sensors directly.
The resistance values are displayed at a resolution of 1 digit per 0.2
Ω
in one word
(16-bit). The maximum number range viewable in one word in two's complement
representation ranges from −32768 to +32767. The number range used depends on
the sensor type set and the resolution of the process value. For the setting
“Resistance measurement 1”, the possible numerical range corresponds to the
defined measuring range of 0 Ohm to 5.0 kOhm and ranges from 0 to +25000
accordingly.
Table 42: ID 14, Setting “Resistance measurement 1”, Standard Format
Resistance
Ω
Numeric value
1)
Status
byte
hex.
Error
LED
Binary
Hex.
Dec.
0
'0000.0000.0000.0000'
0x0000
0
0x00
OFF
100
'0000.0001.1111.0100'
0x01F4
500
0x00
OFF
200
'0000.0011.1110.1000'
0x03E8
1000
0x00
OFF
300
'0000.0101.1101.1100'
0x05DC
1500
0x00
OFF
1000
'0001.0011.1000.1000'
0x1388
5000
0x00
OFF
2000
'0010.0111.0001.0000'
0x2710
10000
0x00
OFF
3000
'0011.1010.1001.1000'
0x3A98
15000
0x00
OFF
4000
'0100.1110.0010.0000'
0x4E20
20000
0x00
OFF
5000
'0110.0001.1010.1000'
0x61A8
25000
0x00
OFF
> 5000
'0110.0001.1010.1000'
0x61A8
25000
0x42
ON
Overrange
3)
> 5010
'0110.0001.1010.1000'
0x61A8
25000
0x62
ON
Wire break
2)
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section “Diagnostics” > „Behavior in
the Event of an Error“)
3) When underrange / overrange limit is ON (see section “Diagnostics” > „Behavior in the Event
of an Error“)