Version 1.1.0
Table 48: Register 35
Register
Function
Memory
Access
Default setting
35
Channel configuration
EEPROM
R/W
0xFF10
Bit 0 … 3: Sensor
Value
Sensor type
Standard
Measuring range
Resolution
0*
Pt100
IEC 751
–200 °C … 850 °C
0.1 °C
1
Ni100
DIN 43760
–60 °C … 250 °C
0.1 °C
2
Pt1000
IEC 751
–200 °C … 850 °C
0.1 °C
3
Pt500
IEC 751
–200 °C … 850 °C
0.1 °C
4
Pt200
IEC 751
–200 °C … 850 °C
0.1 °C
5
Ni1000
TK 61180
DIN 43760
–60 °C … 250 °C
0.1 °C
6
Ni120
Minco
–80 °C … 260 °C
0.1 °C
7
Ni1000
TK 5000
(Staefa)
–60 °C … 250 °C
0.1 °C
8
Ni1000
TK 6180
DIN 43760
–50 °C … 150 °C
0.01 °C
9
Ni1000
TK 5000
(Staefa)
–50 °C … 150 °C
0.01 °C
10
Pt1000
IEC 751
–50 °C … 150 °C
0.01 °C
11
Reserved for expansions
12
Reserved for expansions
13
Reserved for expansions
14
Resistance
measurement 1
0 Ohm … 5 kOhm
0.2 Ohm
15
Resistance
measurement 2
0 Ohm … 1.2 kOhm
0.05 Ohm
Bit 4 … 5: Selection of the operating mode
0
Channel disabled
1*
2-wire
Bit 6: Selection of the calibration data
0*
Manufacturer calibration
1
User calibration
Bit 7: Activation of user scaling
0*
User scaling disabled
1
User scaling enabled
Bit 8: Diagnosis, underrange
0
Diagnostics disabled
1*
Diagnostics enabled
Bit 9: Diagnosis, overrange
0
Diagnostics disabled
1*
Diagnostics enabled
Bit 10: Diagnosis, user limiting value underrange
0
Diagnostics disabled
1*