110 Use in Hazardous Environments
WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Manual
Version 1.1.0
Pos: 48.20 /Serie 750 ( WAGO-I/O-SYST EM)/Ei nsatz i n Ex-Bereichen/Besonder e Beding ung en für den sicher en Ex- Betrieb gem. IEC-Ex-Z ertifi kat TUN 14.0035 X_2014 @ 21\mod_1416995779884_21.docx @ 169122 @ 3 @ 1
10.2.3 Special Conditions for Safe Use (IEC-Ex Certificate TUN
14.0035X)
1.
The modules of the WAGO-I/O-SYSTEM 750-*** have to been erected in
such a way, that corresponding to IEC 60079-15 a degree of protection of at
least IP 54 according to IEC 60529 is achieved.
2.
Measures have to been taken, external to the modules, to provide a transient
protection that ensures that the rated voltage, connected to the power supply
terminals, is not exceeded by more than 40 %.
3.
The connecting and disconnecting of the non-intrinsically safe circuits is
only permitted if no explosive atmosphere exists. This although applies for
the all switches, interfaces (Fieldbus, Ethernet, Serial) and the SD-card.
4.
The ambient temperature range is: 0 °C ≤ Tamb ≤ +60 °C
The ambient temperature range for modules with suffix extension /025-****
is: -20
°C ≤ Tamb ≤ +60 °C