28
Process Image
WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Manual
Version 1.1.0
No short-circuit detection for resistance measurements!
For sensor types “Resistance measurement 1” and “Resistance measurement 2”,
short-circuit detection is not technically possible.
4.3
Process Data
4.3.1
Overview of Sensor Types
The following table serves as an overview of all supported sensor types presented
in standard format and in S5-FB250 format. The following sections provide
detailed information about the individual sensor types ordered by ID. The
information in the respective tables for resolution and measured values, as well as
the resulting raw value ranges are based on the manufacturer scaling.
Table 19: Process Data, Overview in Standard Format and S5-FB250 Format
ID
Sensor type Standard Measuring range
Notation
Standard format
S5-FB250 format
Resolution
Raw value
range
Resolution
Raw value
range
0
Pt100
IEC 751
−200
°C … 850 °C
0.1 °C
−2000 … 8500
0.5 °C
−400 … 1700
1
Ni100
DIN 43760
−60 °C … 250
°C
0.1 °C
−600 … 2500
0.5 °C
−120 … 500
2
Pt1000
IEC 751
−200
°C … 850 °C
0.1 °C
−2000 … 8500
0.5 °C
−400 … 1700
3
Pt500
IEC 751
−200
°C … 850 °C
0.1 °C
−2000 … 8500
0.5 °C
−400 … 1700
4
Pt200
IEC 751
−200
°C … 850 °C
0.1 °C
−2000 …
8500
0.5 °C
−400 … 1700
5
Ni1000
TK6180
DIN 43760
−60
°C … 250 °C
0.1 °C
−600 … 2500
0.5 °C
−120 … 500
6
Ni120
Minco
−80 °C … 260
°C
0.1 °C
−800 … 2600
0.5 °C
−160 … 520
7
Ni1000
TK5000
(
Staefa)
−60
°C … 250 °C
0.1 °C
−600 … 2500
0.5 °C
−120 …
500
8
Ni1000
TK6180
DIN 43760
−50
°C … 150 °C
0.01 °C
−5000 … 15000
0.05 °C
−1000 … 3000
9
Ni1000
TK5000
(
Staefa)
−50
°C … 150 °C
0.01 °C
−5000 … 15000
0.05 °C
−1000 … 3000
10
Pt1000
IEC 751
−50
°C … 150 °C
0.01 °C
−5000 … 15000
0.05 °C
−1000
… 3000
11
Reserved for expansions
12
Reserved for expansions
13
Reserved for expansions
14
Resistance
measuring
range 1
–
0 Ohm … 5 kOhm
0.2 Ohm
0 … 25000
4 Ohm
0 … 1250
15
Resistance
measuring
range 2
–
0 Ohm … 1.2 kOhm
0.05 Ohm
0 … 24000
0.5 Ohm
0 … 2400