Process Image
WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Manual
Version 1.1.0
4.3.3.2 S5-FB250 Format
With the setting “Ni100 (DIN 43760)” and activated S5-FB250 format, the I/O
module converts the measured resistance values of Ni100 sensors (DIN 43760)
into temperature values and outputs the conversion results.
The temperature values are displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.
Table 23: ID 1, Setting Ni100 (DIN 43760), S5-FB250 Format
Temperature
°C
Resistance
Ω
Numeric value
1)
with status information
4)
Status
byte
hex.
Error
LED
Binary
XFÜ
Hex.
Dec.
---
< 10.00
'1111.1100.0100.0 010'
0xFC42
−958
0x50
ON
Short circuit
2)
< −60.0
< 69.52
'1111.1100.0100.0 001'
0xFC41
−959
0x41
ON
Underrange
3)
−60.0
69.52
'1111.1100.0100.0 000'
0xFC40
−960
0x00
OFF
−50.0
74.26
'1111.1100.1110.0 000'
0xFCE0
−800
0x00
OFF
0.0
100.00
'0000.0000.0000.0 000'
0x0000
0
0x00
OFF
50.0
129.11
'0000.0011.0010.0 000'
0x0320
800
0x00
OFF
100.0
161.78
'0000.0110.0100.0 000'
0x0640
1600
0x00
OFF
150.0
198.64
'0000.1001.0110.0 000'
0x0960
2400
0x00
OFF
200.0
240.66
'0000.1100.1000.0 000'
0x0C80
3200
0x00
OFF
250.0
289.16
'0000.1111.1010.0 000'
0x0FA0
4000
0x00
OFF
>250.0
> 289.16
'0000.1111.1010.0 001'
0x0FA1
4001
0x42
ON
Overrange
3)
---
> 5010.00
'0000.1111.1010.0 010'
0x0FA2
4002
0x60
ON
Wire break
2)
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section “Diagnostics” > “Behavior in
the Event of an Error”)
3) When underrange / overrange limit is ON (see section “Diagnostics” > “Behavior in the Event
of an Error”)
4) Status information:
X: Not used,
F: Short circuit, wire break,
Ü: Underrange, overrange