Commissioning
06/13
185
Check that ...
1. the pipe system is firmly connected to the pipe connection of TITANUS
®
.
2. all pipe fittings are glued and the pipe system is air tight. For this pur-
pose, first seal all air sampling points (e.g. with insulating tape). Then
measure the air flow at the opening for the air return.
3. the correct aspiration-reducing film sheets were taped over the air sam-
pling points.
NOTICE
After adjusting the air flow sensors (chapter “Air Flow Sensor Adjustment“)
no further alterations must be made to the pipes.
If later alterations become necessary, the air flow sensor must be read-
justed.
To carry out the operational check, optional diagnostic software DIAG 3 can
be used.
Follow these steps:
1. Install the diagnostic software on a laptop or PC. WINDOWS 95, 98, ME,
2000, NT, XP, Vista or 7 are suitable.
2. With the enclosed diagnostic cable TITANUS
®
is connected to the PC
via “Diag.” on the main board.
3. The diagnostic software is started up.
4. The monitor of the PC displays the current data of TITANUS
®
visualized
.
NOTICE
For a correct colour interpretation, the monitor and graphic card must be
able to depict more than 256 colours.
After completion of the operations check, commissioning of the device with
the pipe system must be repeated from chapter "Adjustment of Air Flow
Sensor.
Connection check
Содержание TITANIUS TOP-SENS
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Страница 16: ......
Страница 56: ......
Страница 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Страница 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Страница 127: ...TITANUS TOP SENS Rev a Installation 06 13 127 Figure 69 Borehole spaces of the support type MT 1 ...
Страница 130: ...Installation TITANUS TOP SENS Rev a 130 06 13 Figure 71 General outlay of the terminal blocks of the circuit board ...
Страница 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Страница 148: ......
Страница 156: ...Installation of the pipe system TITANUS TOP SENS Rev a 156 06 13 Figure 88 Attaching the aspiration reducing film sheet ...
Страница 204: ......
Страница 206: ......
Страница 210: ......
Страница 216: ......
Страница 226: ......
Страница 240: ......
Страница 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Страница 247: ......
Страница 248: ......
Страница 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Страница 250: ...TITANUS TOP SENS Rev a ...