Installation of the pipe system
TITANUS
TOP·SENS
®
/Rev.a
170
06/13
Steam trap
Steam trap type KA-DN-25
Figure 99: Installation of steam trap type KA-DN-25 to pipe system
Install the steam trap at the lowest point of the pipe system behind the air fil-
ter and TITANUS
®
- device and fasten it with PG screw joints.
NOTICE
Two 45º elbows are required on each connection end for the installation of
the steam trap to the pipe system.
When installing the steam trap, note the direction of air flow (see arrow on
housing of steam trap).
1. Prepare the pipe system with two 45° elbows at each end of the steam
trap and connect it to the PG screw joints.
2. Additionally, secure the steam trap with two screws and the support.
7.10
7.10.1
Connection
Содержание TITANIUS TOP-SENS
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Страница 16: ......
Страница 56: ......
Страница 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Страница 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Страница 127: ...TITANUS TOP SENS Rev a Installation 06 13 127 Figure 69 Borehole spaces of the support type MT 1 ...
Страница 130: ...Installation TITANUS TOP SENS Rev a 130 06 13 Figure 71 General outlay of the terminal blocks of the circuit board ...
Страница 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Страница 148: ......
Страница 156: ...Installation of the pipe system TITANUS TOP SENS Rev a 156 06 13 Figure 88 Attaching the aspiration reducing film sheet ...
Страница 204: ......
Страница 206: ......
Страница 210: ......
Страница 216: ......
Страница 226: ......
Страница 240: ......
Страница 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Страница 247: ......
Страница 248: ......
Страница 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Страница 250: ...TITANUS TOP SENS Rev a ...