Commissioning
TITANUS
TOP·SENS
®
/Rev.a
184
06/13
Carrying out operational check
The operational check can be carried out with or without a digital manome-
ter. The complete check is described below. If, during the operational check
of TITANUS
®
, the values vary from those described, the device or its air flow
sensor are damaged.
1. After about 120 seconds activate the flow-init button on the detector
module. The operating display flashes and the fault display must go out
(see INSTRUCTION).
2. After a short initiation period the depression generated in the device is to
be approx. 250 up to 310 Pa for a set fan voltage of 6.9 V and 460 up to
530 Pa for 9 V. The LED flash code on the detector module’s electronics
board must indicate „Blockage“ after a few seconds (see INSTRUC-
TION).
3. Re-open all air sampling points of the test pipe. After a few seconds the
LED flash code must go out.
4. Remove the test pipe. After a few seconds the LED flash code on detec-
tor modules I and II must indicate „Fracture“.
5. Re-connect the test pipe to the device. After a few seconds the LED
flash code must go out.
NOTICE
A pipe fracture or blockage is indicated by a flashing LED on detector mod-
ule I and II:
- Fracture: 3x flashing
- Blockage: 2x flashing
The relevant flash code is repeated every two seconds.
NOTICE
For TITANUS
®
the operational check with steps 1 to 5 must be carried out
for both pipe systems.
If no fault was registered during the operational inspection, the smoke detec-
tion system must be checked.
8.5.2
Содержание TITANIUS TOP-SENS
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS TOP SENS Rev a Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...TITANUS TOP SENS Rev a Rev a 12 06 13 ...
Страница 16: ......
Страница 56: ......
Страница 62: ...Design TITANUS TOP SENS Rev a 62 06 13 Figure 32 Pipe designs ...
Страница 72: ...Design TITANUS TOP SENS Rev a 72 06 13 ...
Страница 127: ...TITANUS TOP SENS Rev a Installation 06 13 127 Figure 69 Borehole spaces of the support type MT 1 ...
Страница 130: ...Installation TITANUS TOP SENS Rev a 130 06 13 Figure 71 General outlay of the terminal blocks of the circuit board ...
Страница 140: ...Installation TITANUS TOP SENS Rev a 140 06 13 Figure 77 Connecting the TITANUS ...
Страница 148: ......
Страница 156: ...Installation of the pipe system TITANUS TOP SENS Rev a 156 06 13 Figure 88 Attaching the aspiration reducing film sheet ...
Страница 204: ......
Страница 206: ......
Страница 210: ......
Страница 216: ......
Страница 226: ......
Страница 240: ......
Страница 246: ...TITANUS TOP SENS Rev a Glossary TS_A_Glossar en e DOC Data 04 09 ...
Страница 247: ......
Страница 248: ......
Страница 249: ...TITANUS TOP SENS Rev a 06 13 205 ...
Страница 250: ...TITANUS TOP SENS Rev a ...