LED BLINK
SYMPTOM
TEST / DIAGNOSIS
CORRECTIVE
CODE
ACTION
Compressor and fan do not
No power to unit / Blown fuse
Replace MAIN fuse (15 amp).
attempt to start
Correct wiring refer to manual
Reverse polarity
Correct polarity
3
Pressure too high
Wait, try again
3
Faulty electronic module
Replace module
Faulty compressor
Call WAECO USA (860.664-4911)
2
Faulty / shorted delay
Replace PCB inside stainless
steel electrical box
1
Compressor and fan attempt
Low voltage at unit: C/o=9.6V
Charge battery
to start as shown by momentary
C/in=11.0V
voltage dip, fan movement or
compressor vibration
1
Excessive voltage drop from battery
Correct wiring (refer to manual)
to unit during start-up attempt
3,4
Internal refrigerant pressures
Shut off power, wait 15 minutes,
not yet equalized
restore power
Faulty electronic module
Replace electronic module
3
Faulty compressor
Call factory
5
Excessively hot electronic module
Improve air flow to unit
4,5
Overheated compressor
Improve air flow to unit
2
Compressor does not run,
Defective or shorted relay or
Replace PCB inside stainless steel
fan does not run
wiring drawing over 0.5 amps
electrical box
activates protective circuit in electronic
module
Fan / Pump fuse blows
Replace fuse (5 amp)
Faulty fan
Replace fan
Faulty wiring to fan
Repair wiring fault
Fan okay, but module faulty
Replace electronic module
test by putting 12V to fan directly
Intermittent compressor/
Poor electrical supply, chronic
Review manual, correct wiring
fan operation
voltage fluctuations
faults, recharge or replace battery
Faulty control module
Replace control module
Faulty compressor
Call WAECO USA (860.664-4911)
Power duct fan does not run
Faulty fan (test with 12V DC power
Replace fan
source)
Faulty wiring to power duct fan
Repair wiring
TROUBLESHOOTING