background image

Contents, specifications and availability are subject to change without notice.

Tel. (860) 664-4911 • Fax. (860) 664-4912 • www.waecousa.com    

WAECO USA, Inc. 

15

MOUNTING THE POWERPLATE

1. Plan the installation to position the PowerPlate in the

preferred orientation: on a vertical wall of the refriger-
ator (or freezer) cabinet with the label on top. In this
position, the PowerPlate will perform at maximum
efficiency. If this is not possible, it may be installed in
any spatial orientation; but a small reduction of 
efficiency may result.

2. Position the PowerPlate high in the compartment—

within 2 inches of the top for best results.

3. Be sure to leave room for mating and tightening the

couplings that connect the PowerPlate to the tube set.

4. Mark and drill four (4) mounting holes using a 9/64”

drill and a tube exit hole using a 1-1/2” hole saw.

5. Be sure to use the supplied four (4) plastic spacers to

ensure that the PowerPlate is spaced away from the
cabinet wall to permit air circulation behind it for best
efficiency. Do not mount the PowerPlate flush against
the wall as a major loss of performance will result.

POWER PLATE TUBE SET

Drill a 1-1/2” diameter hole through the cabinet wall for
the tube set. Unroll the tube set. Feed the end with the
couplings into the box. Do not remove the protective caps
yet.
Position the insulating sleeving 

OUTSIDE

(not inside) the

refrigerated space. The end of the sleeve should butt
against the outside wall of the box (you will be sealing
this joint later with mastic putty included in your kit.)
Route the service port coupling ends of the tube set
through the boat to the condensing unit. Do not remove
the protective caps yet. 

Before you connect the refrigerant couplings to the
power plate, refer back to the section entitled
“Refrigerant Couplings” for additional information. Have
the required 5/8 and 3/4 wrenches at hand now. Do not
allow any dirt, sawdust, foam insulation dust, etc., to get
into couplings ends as this will seriously damage the 
system.

These couplings are different from the couplings that join
the tube set to the condensing unit. The small couplings
are screwed, o-ringed, and 

LocTite-sealed to the bases

that are in-turn soldered to the copper tubes. Therefore,
it is most important that you do not unscrew the small
couplings from their bases. 

Put your wrenches on the

coupling bodies only!

SMALL COUPLING TORQUE REQUIRED

12–15 foot pounds (less than the large couplings)

CONNECTING THE PLATE COUPLINGS 

(from tube set to

PowerPlate)
1. Remove the protective caps of one mating pair of the

couplings inside the box (start with 

either pair). Screw the

couplings halves together until they bottom metal-to-metal
with very firm pressure (about 4 turns) using two wrenches:
5/8” and 3/4”.

2. Mark the coupling halves. Using your two wrenches (do not

use pliers, visegrips, etc) tighten couplings an additional one
flat (1/6 turn). This should require considerable wrench
torque. If it did not, you did not “bottom” the couplings first.

3. Repeat the above for the other pair of coupling halves.

IMPORTANT:

Save all coupling protective caps. Put them in a

marked container and keep aboard. If a future service procedure
requires that any coupling pair be disconnected, these caps must
be re-installed immediately to keep out dirt.
To connect the couplings to condensing unit, please refer to
section entitled “Refrigerant Couplings.” After completing this
section, seal the black rubber insulating sleeve to the outside of
the refrigerated box airtight, using 

Mortite or other (removable-

type) caulking sealant. All three (3) feet of sleeve must be
outside the box. This sleeve may butt against the outer wall or
the inner liner.

Excess tubing: Form a coil about 18” in diameter, (taking care not
to deform the tubes) in the horizontal orientation if possible, and
secure tightly to the bulkheads, etc. using plastic wire straps.
Protect tubing from chafe and vibration with soft sleeving as
necessary.

Содержание ADLER /BARBOUR SERIES

Страница 1: ...e subject to change without notice Tel 860 664 4911 Fax 860 664 4912 www waecousa com WAECO USA Inc 1 WAECO USA Clinton CT www waecousa com Installation Operating Manual For ADLER BARBOUR SERIES ColdM...

Страница 2: ...Considerations 16 Water Cooled Optional Package Installation 17 Battery Recommendations 18 Wiring the System 18 Voltage Drops 19 Making the Power Connections 19 Wire Size and Wire Size Table 19 Wiring...

Страница 3: ...efficiency with minimal power consumption TERMINOLOGY Below are terms and definitions that will be used throughout this manual CONDENSING UNIT The stainless steel base plate mounted compressor electr...

Страница 4: ...ollowing points in mind when planning the installation GENERAL The connecting refrigerant tube set between the condensing unit and the freezer is 15 long 12 5 for PowerPlate Plan the location of the t...

Страница 5: ...ible location in the largest compartment available However many other locations are acceptable provided the appropriate ventilation duct kit is installed see below ENGINE COMPARTMENT DUCT KIT OR POWER...

Страница 6: ...TE The bracket may seem too light and flexible before it is mounted Once bolted securely to the bulkhead then use supplied bolts to secure the condensing unit base it becomes stabilized and very rigid...

Страница 7: ...You may need to install a manual damper over the hole to better control individual compartment temperatures This can be a simple disc with a single pivot screw As an alternative you can use the Adler...

Страница 8: ...up to 6 cubic feet with box insulation 4 or better 8 cubic feet with insulation of 6 or better REFRIGERATOR The standard small vertical or small horizontal evaporator is used for refrigerators up to...

Страница 9: ...keeps the tubing feeding smoothly without damaging it Be careful not to kink flatten or strain joints Make sure the plastic caps are in place over the refrigerant couplings Keep dirt out of the coupl...

Страница 10: ...he excess tubing and the thermostat wiring harness in an 18 to 24 diameter coil and secure preferably in a horizontal orientation Support the refrigerant tube set and the wire harness using clamps and...

Страница 11: ...away view of the male and female coupling halves being joined at 20 50 and 100 connection NOTE the way the cutter blades pierce the diaphragms and fold them back out of the flow path Also note the dif...

Страница 12: ...CW Clockwise the female until the coupling halves bottom out and strong resistance is felt THIS WILL REQUIRE ABOUT 6 FULL TURNS Work rapidly to minimize any possible escape of refrigerant past the tem...

Страница 13: ...hrough the thermostat flange holes INSTALLATION PROCEDURE see drawing below 1 Carefully unroll just enough capillary tubing to reach the metal and plastic clamp plates on the side of the freezer unit...

Страница 14: ...rovided MOUNTING THE TEMPERATURE SENSING BULB 1 Run the sensing bulb and wire into the refrigerated box to be controlled Mount the sensing bulb on a box side wall midway between top and bottom using t...

Страница 15: ...d now Do not allow any dirt sawdust foam insulation dust etc to get into couplings ends as this will seriously damage the system These couplings are different from the couplings that join the tube set...

Страница 16: ...he switch panel provided with this option note that the built in fan and the Powerduct fan if fitted continues to run This ensures a flow of air over the compressor to keep it relatively cool and is n...

Страница 17: ...d that the seacock is at least 2 below the waterline 5 Inlet thruhull must have a scoop facing forward on the outside of the hull to prevent back siphoning At high sailing speeds the flow direction ma...

Страница 18: ...a battery constructed to provide small to moderate currents for long periods of time as opposed to short bursts of high current to start engines While deep cycle batteries start engines quite satisfa...

Страница 19: ...breaker to prevent voltage drops in the supply circuit to the ColdMachine Also do not install voltage dropping devices such as indicator lights volt and amp meters etc in the 12 volt DC wiring circui...

Страница 20: ...20 WAECO USA Inc Tel 860 664 4911 Fax 860 664 4912 www waecousa com Contents specifications and availability are subject to change without notice...

Страница 21: ...Contents specifications and availability are subject to change without notice Tel 860 664 4911 Fax 860 664 4912 www waecousa com WAECO USA Inc 21...

Страница 22: ...22 WAECO USA Inc Tel 860 664 4911 Fax 860 664 4912 www waecousa com Contents specifications and availability are subject to change without notice...

Страница 23: ...Contents specifications and availability are subject to change without notice Tel 860 664 4911 Fax 860 664 4912 www waecousa com WAECO USA Inc 23...

Страница 24: ...thick frost formation is an indication of moist outside air entering through a poorly sealed lid doors or liner joints These conditions must be eliminated for proper performance The best way to defro...

Страница 25: ...at Do not set a positive differential Do not set a differential of 0 zero HIGH LOW SET POINT LIMITS HI LO Allow you to limit the range at which temperature set points can be programmed This is factory...

Страница 26: ...E FLASHING LED ON THE CONDENSING UNIT If the electronic module senses a malfunction it will auto matically switch into its protective mode and will make repeated start attempts at about 1 minute inter...

Страница 27: ...ressures Shut off power wait 15 minutes not yet equalized restore power Faulty electronic module Replace electronic module 3 Faulty compressor Call factory 5 Excessively hot electronic module Improve...

Страница 28: ...ing sleeve Partial clog in refrigerant circuit Call WAECO USA 860 664 4911 only part of the evaporator is frosting 3 Box insulation is inadequate or Re insulate Contact local dealer box too large for...

Страница 29: ...rtition between well insulated evaporator and perishable food section Thermostat sensing bulb not See manual correct mounted correctly Water pump runs no water flow Air in pump cannot self purge Check...

Страница 30: ...fins are soft and thin for maximum efficiency PROCEDURE FOR REMOVING EVAPORATOR AND TUBE SET 1 Turn the thermostatic control to OFF 2 Disconnect the 12V DC power supply to the compressor unit Carefull...

Страница 31: ...also have other rights which vary from State to State THERE ARE NO OTHER WARRANTIES OF MERCHANTABILITY FITNESS FOR PURPOSE OR ANY OTHER KIND ANY EXPRESSED OR IMPLIED ARE HEREBY DISCLAIMED AND EXCLUDED...

Страница 32: ...WAECO USA Inc P O Box 497 8 Heritage Park Road Clinton CT 06413 Tel 860 664 4911 Fax 860 664 4912 www waecousa com...

Отзывы: