Use of Extension Cords
When a long extension cord is used to connect an appliance or tool to the
generator, a voltage loss occurs—the longer the cord, the greater the voltage loss.
This results in less voltage being supplied to the appliance or tool and increases
the amount of current draw or reduces performance. A heavier cord with a larger
wire size will reduce the voltage loss.
Damaged extension cords can cause electrical shock, resulting in serious injury or
death. DO NOT use worn, bare, or frayed cords. Replace damaged cords
immediately.
Use the chart below as a guide for selecting proper cable size.
Use only extension cords rated for outdoor use and equipped with a third-wire
ground.
NOTICE
:
Operating equipment at low voltage can cause it to overheat.
Current
Load in Watts
Maximum Cable Length in Feet
(Amps)
120V
240V
#10
#12
#14
#16
2.5
300
600
1000.
600
375
250
5
600
1200
500
300
200
125
7.5
900
1800
350
200
125
100
10
1200
2400
250
150
100
—
15
1800
3600
150
100
65
—
20
2400
4800
125
75
50
—
WARNING
Содержание GP 4000
Страница 1: ...5000192915 02 0813 5 0 0 0 1 9 2 9 1 5 Operator s Manual Portable Generator GP 4000 EN...
Страница 6: ...Foreword GP 4000 6 wc_tx003404gb fm...
Страница 18: ...wc_si000792gb fm 18 Labels GP 4000 2 Labels 2 1 Label Locations wc_gr010975 A B C D E F J K H L G...
Страница 31: ...wc_tx003406gb fm 31 GP 4000 Operation wc_gr010938 a b c d e f g h j k l m n o p 1 l l n...
Страница 50: ...wc_td000566gb fm 50 Technical Data GP 4000 Notes...
Страница 59: ...Emission Control Systems Information and Warranty wc_tx001773gb fm 59...
Страница 60: ...Emission Control Systems Information and Warranty 60 wc_tx001773gb fm...
Страница 61: ...Schematics wc_tx003409gb fm 61 9 Schematics...
Страница 67: ......