5.2.4
PASSFB (Password for fieldbus)
Command
Parameters
Unit
Group
PASSFB
x
x
= 0… 10000000
-
SYSTEM
The value inputted here serves as password for the parameterising function via fieldbus. In order to enable a
parametrization, it has to be sent via fieldbus to the relating address. If
PASSFB
is
“0” (factory setting) the
password protection is not active.
5.2.5
EOUT (Output signal if READY = OFF)
Command
Parameters
Unit
Group
EOUT x
x= -
10000… 10000
0.01 %
SYSTEM
Output value in case of a detected error or a deactivated ENABLE input. This function can be used if the drive
has to be moved to one of the two end positions (with defined speed), e.g. in case of an sensor error.
|EOUT| = 0
The output is switched off in the event of an error. This is normal behavior.
5.2.6
HAND (Manual speed)
Command
Parameters
Unit
Group
HAND:i
x
i= A|B
x= -
10000… 10000
0.01%
SYSTEM
The manual speeds are set with these parameters. The drive moves in a controlled manner in the defined
direction when the manual signal is active. The direction is defined by the sign of the parameters. After the
manual signal has been disabled, the drive remains under control in the current position.
In case of a fault (position sensor fault), the drive can still be moved with the manual function. The output will
be switched off when hand signals are turned off.
The manual speed is also limited by the (internal or external) speed demand (MIN evaluation).
Caution!
Do not use the manual mode in conjunction with the EOUT command. After the
deactivation of the HAND input the output is set to the EOUT value.