VRG CONTROLS LLC.
7 of 39
MAY 2021
RCVC 3000 - Red Circle Valve Controller
Installation, Operation, Maintenance Manual
PUSH to enter.
12. Select “Maximum” and SHORT PUSH to enter.
13. Use VMO or other method Stroke control valve
to VALVE CLOSED (MAX) position and SHORT
PUSH to enter.
14. Rotate Navigation Wheel to ESC Position to
reselect NEW CALIBRATION.
15. Rotate Navigation Wheel Toward (CCW) to
select SAVE CALIBRATION and SHORT PUSH
to enter.
16. Rotate Navigation Wheel to HOLD ESC Position
until menu stops at MANUAL on DISPLAY
HEADER.
17. Return Navigation Wheel to Neutral (Center)
Rotation Position. SHORT PUSH Navigation
Wheel on RCVC Head to exit MANUAL mode.
RCVC display Header should read AUTOMATIC.
#4 Retransmission Signal Calibration
1. Apply 24 VDC Power Supply to RCVC
2. SHORT PUSH Navigation Wheel on RCVC Head
to enter Manual mode.
3. LONG PUSH Navigation Wheel on RCVC Head to
enter MENU mode.
4. Select “Application” and SHORT PUSH to enter.
5. Select “Physical I/O” and SHORT PUSH to enter.
6. Select “Analogue Outputs” and SHORT PUSH to
enter.
7. Select “Feedback” and SHORT PUSH to enter.
8. Select “Calibration” and SHORT PUSH to enter.
9. Select “New Calibration” and SHORT PUSH to
enter.
10. Select “Minimum” and SHORT PUSH to enter.
11. Use Navigation Wheel to set the Value so the
Output is equal to 4 ma, then SHORT PUSH to
save value.
12. Select “Maximum” and SHORT PUSH to enter.
13. Use Navigation Wheel to set the Value so the
Output is equal to 20 ma, then SHORT PUSH to
save value.
14. Rotate Navigation Wheel to ESC Position to
reselect NEW CALIBRATION.
15. Rotate Navigation Wheel Toward (CCW) to
select SAVE CALIBRATION and SHORT PUSH
to enter.
16. Rotate Navigation Wheel to HOLD ESC Position
until menu stops at MANUAL on DISPLAY
HEADER.
17. Return Navigation Wheel to Neutral (Center)
Rotation Position. SHORT PUSH Navigation
Wheel on RCVC Head to exit MANUAL mode.
RCVC display Header should read AUTOMATIC.
#5 Reverse Valve Action
1. Apply 24 VDC Power Supply to RCVC
2. Apply Command Signal to RCVC
3. SHORT PUSH Navigation Wheel on RCVC Head
to enter MANUAL mode.
4. LONG PUSH Navigation Wheel on RCVC Head to
enter MENU mode.
5. Select “Application” and SHORT PUSH to enter.
6. Select “Physical I/O” and SHORT PUSH to enter.
7. Select “Analogue Inputs” and SHORT PUSH to
enter.
8. Select “Command Signal” and SHORT PUSH to
enter.
9. Select “Sensor Range” and SHORT PUSH to
enter.
10. Select “Minimum” and SHORT PUSH to enter.
11. Use Navigation Wheel TOWARD (CCW) to ad
just value to 100% on Minimum. SHORT PUSH
to enter.
12. Select “Maximum” and SHORT PUSH to enter.
13. Use Navigation Wheel AWAY (CW) to adjust
value to 0.0% on Minimum. SHORT PUSH to
enter.
14. Rotate Navigation Wheel to HOLD ESC Position
until menu stops at MANUAL on DISPLAY
HEADER.
15. Return Navigation Wheel to Neutral (Center)
Rotation Position. SHORT PUSH Navigation
Wheel on RCVC Head to exit MANUAL mode.
RCVC display Header should read AUTOMATIC.