VRG CONTROLS LLC.
31 of 39
MAY 2021
RCVC 3000 - Red Circle Valve Controller
Installation, Operation, Maintenance Manual
Figure 8: Spring to Open Ball Control V
alve with RCVC, VMO & Balluff
TRM: XA-6018-AP01
C L O S E
222
3
1
3
22
1
2
4-20 mA INPUT 4-20 mA FEEDBACK
"OPEN"
"CLOSE"
24 VDC
ASCO EV8327; SS Low Temperature (-40C); 24VDC
EX
Spring to Open Control Ball Valve
Balluff Transmitter
EX
VRG RCVC Controller
EX Terminal Box
Gas Supply 1500 psig Max.
Set at 150 psig Max.
Relief Valve
1/2 NPT Check Valve
Sol.#1
Sol.#2
Orifice
C
REV.
DESCRIPTION
DATE
BY
A
FIRST RELEASE
11/17/2018
VE
B
CHECK VALVE ADDED
12/4/2020
AFB
D
C
B
A
A
B
C
D
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
THE INFORMATION CONTAINED IN THISDRAWING IS THE SOLE PROPERTY O
F
VRG.
CONTROLS LLC
.
ANY REPRODUCTION IN PART OR AS A WHOLEWITHOUT THE
WRITTEN PERMISSION OF
VRG. CONTROLS LLC
IS PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
DRAWN
REVISED
ENG APPR.
TITLE:
SIZE
B
DWG. NO.
REV
VR
CODE:
XA-6018-AP01
NOTE:
CUSTOMER:
JOB #:
PO#:
RCVC-ASCOEV8327NC-ASCOEV8327NO-VMO-
BLF/FOB
1/4 NPT FULL PORT BALL VALVE
1/4 NPT INSTRUMENT BALL VALVE
1/4 NPT M & F NEEDLE VALVE
1/4 NPT FIELD CONNECTION
1/4" TUBING OR 1/4" NPT FITTING CONNECTION
3/8" TUBING 1/2" TUBING
N/A
N/A
N/A
AFB
12/4/2020
Spring to Open Ball Control Valve with RCVC, VMO
& Balluff TRM
PR0JECT :
VLV #:
CD#:
N/A
N/A
1. Valve Will Stay in Last Position or Open, or Close on
Loss of 4-20 mA
Signal. Menu Selectable.
2. Customer Conn/- 24 VDC, 4-20 mA Input, 4-20 mA Fee
dback.
3. Control Valve is Fail Open on loss of 24 VDC.
N/A
11/17/2018
VE