VII.3.8.f BACNET IP type B communication
To activate BACNET and change the parameters (fixed IP, name of controller…), download the appropriate E-tool software
or the lightweight WEB configuration software from: http://www.regin.se (download tab)
You will find the complete WEB variables list at: http://www.regin.se.
VIII REPAIR
VIII.1 Various examples of faults
The Regulation of the VORT NRG EC units is equipped with alarms. When the red LED blinks, press on the alarm button
(red) to display the fault.
Faults are classified into class A, B or C (see details below)
Type of fault:
A: The fault stops the ventilation system. The device does not start until the problem is solved and the fault is eliminated.
B: The fault does not stop the ventilation system. To clear the alarm, the fault must be eliminated. It remains in the the log
but does not prevent the system from functioning.
C: The fault does not stop the ventilation system and disappears automatically as soon as the problem is resolved.
ENGLISH
Description of fault
Cause
CORRIGO screen not lighting
Power supply to unit is incorrect (P/B LED of CORRIGO off)
- To light screen, press on a key (back-lighting).
The fan(s) is/are not working
The clocks are at 0 or you have no external start order
Remote control is not working or
is giving wrong values
Remote control wire not original (wire changed, shortened or extended)
Repeater wrongly connected
32
Содержание VORT NRG EC 3000
Страница 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Страница 38: ...ENGLISH BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 metres Ext Disp OU 38...
Страница 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Страница 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Страница 54: ...54 NOTE ENGLISH...
Страница 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Страница 85: ...FRAN AIS BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 m tres Ext Disp OU 85...
Страница 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Страница 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Страница 101: ...101 IX NOTE FRAN AIS...
Страница 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Страница 132: ...DEUTSCH BMS Standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 Meter Ext Disp OU 132...
Страница 133: ...DEUTSCH SIGNALVERST RKER RS485 100 Meter Max 6 Steuereinheiten MASTER Ext Disp SIGNALVERST RKER 133...
Страница 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Страница 148: ...148 IX NOTE DEUTSCH...