VII.3 Modification of parameters
VII.3.1 Access to blocked parameters
Some parameters are blocked by a password; in this case, when you would like to modify them by pressing the OK key,
this screen will appear.
Enter the code 3333 using the arrow keys and then confirm with the OK key. Press twice on left arrow to access the
menus. In case of an operating error, press twice on the C key and restart the operation.
VII.3.2 Setting different dates and times on the clocks (password required)
VII.3.2.a Date and time of the
CORRIGO
regulator
(1)
section VII.22
Date and time of the regulator are configured by default in the CORRIGO. Change to summer/winter time is managed
automatically. If you need to modify this data, follow the procedure described below:
• Move the cursor to the Time/Date menu as described in section VII.2.
• Once in this menu, press the OK key.
• Enter the desired value.
• Validate by pressing the OK key to go to the
next field.
• Once all the values are updated, press on the left arrow to return to the welcome screen.
VII.3.2.b Programming the system’s operating timetable
(2) (3)
section VII.2
The system is set to work at normal speed from 6.00 am to 10.00 pm and at reduced speed from 10.00 pm to 6.00 am.,
except in
VORT NRG EC DIVA
/
LOBBY
and
QUATTRO
, which is set at permanent reduced speed (night cooling
function active). If you would like to modify the operating hours (stop between 12.00 and 2.00 pm etc.), follow the
procedure set out below):
• Move the cursor to the prog. menu. Normal speed or reduced speed as specified in section VII.2.
• Once in this menu, press the OK key.
• Enter the desired value.
• Validate by pressing the OK key to go to the
next field.
• Use the down arrow to go to the next day. (note:
you will be able to set 2 periods each day for each day of the week and allow 2 periods for vacation days).
• As indicated in the table, you can also modify the periods from Monday to Friday by pressing on the right key when
you are on the screen for Monday, see chapter VII.2.
• Once all the values are updated, press on the left arrow to return to the welcome screen.
Note: if reduced speed (LS) and normal speed (HS) are active in the same time slot, the unit will operate at HS
Operating exceptions:
VORT NRG EC DIVA
and
QUATTRO
: In order for the CO
2
control to work, no normal speed time slot should be active.
LOBBY
: Only the reduced speed clock is active
VII.3.2.c Vacation period
(4)
section VII.2
The system is set with no vacation period. If you would like to reduce the operating time during vacation periods, set the
vacation operating times as described in section VII.3.2.b, then set your vacation days.
Follow the procedure set out below:
• Move the cursor to the Vacation menu as described in section VII.2.
• Once in this menu, press the OK key.
• Enter the desired value.
• Validate by pressing the OK key to go to the next
field.
• Use the down cursor to go to subsequent
periods. (note: you can set up to 24 vacation periods).
• Once all the values are updated, press on the left arrow to return to the welcome screen
ENGLISH
Enter password of the desired authorisation level
Password: ****
Level: Without
Time: e.g.:
10:33
Date: e.g.:
08/12/23
(year/month/day)
Day: e.g.:
Tuesday
Normal speed or reduced speed
Monday
Per1: e.g.:
07:00 - 12:15
Per2: e.g.:
14:00 - 18:00
!
Vacation (month/day)
1: e.g.:
12:20 - 12:27
(from 20 to 27 Dec.)
2: e.g.:
01:05 - 01:05
(1 May)
27
Содержание VORT NRG EC 3000
Страница 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Страница 38: ...ENGLISH BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 metres Ext Disp OU 38...
Страница 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Страница 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Страница 54: ...54 NOTE ENGLISH...
Страница 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Страница 85: ...FRAN AIS BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 m tres Ext Disp OU 85...
Страница 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Страница 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Страница 101: ...101 IX NOTE FRAN AIS...
Страница 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Страница 132: ...DEUTSCH BMS Standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 Meter Ext Disp OU 132...
Страница 133: ...DEUTSCH SIGNALVERST RKER RS485 100 Meter Max 6 Steuereinheiten MASTER Ext Disp SIGNALVERST RKER 133...
Страница 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Страница 148: ...148 IX NOTE DEUTSCH...