ENGLISH
Temperature regulation
Ext. temp.:
Supply air temp.
Actual:
Set point
Set point:
Outdoor comp. set-point
-20°C =
25°C (7)
-15°C =
24°C (7)
-10°C =
23°C (7)
Outdoor comp. set-point
-5°C =
23°C (7)
0°C =
22°C (7)
5°C =
20°C (7)
Outdoor comp. set-point
10°C =
18°C (7)
15°C =
18°C (7)
Frequency control
AS manual ventilation
Output 1/1:
70% (5)
Output 1/2:
50% (5)
...
VAS pressure control system
Set point 1/1: not used
Set point 1/2:
180 Pa (5)
...
VAS airflow control system
Set point 1/1:
5000 m3/h (5)
Set point 1/2:
2500 m3/h (5)
...
Frequency control
AR manual ventilation
Output 1/1:
70% (5)
Output 1/2:
50% (5)
...
VAR pressure control system
Set point 1/1: not used
Set point 1/2:
180 Pa (5)
...
VAR airflow control system
Set point 1/1:
5000 m3/h (5)
Set point 1/2:
2500 m3/h (5)
...
Return air temperature
Actual:
...
Frequency control
(VORT NRG EC
o
DIVA)
AS manual ventilation
Output:
70 (5)
%
or
VAS pressure control system
(VORT NRG EC LOBBY)
Actual: 183 Pa (example)
Set point:
180 Pa (5)
or
VAS airflow control system
(VORT NRG EC MAC2
o
QUATTRO)
Actual: 4178 m3/h (example)
Set point:
5000 m3/h (5)
Frequency control
(VORT NRG EC
o
DIVA)
AR manual ventilation
Output:
70 (5)
%
or
VAR pressure control system
(VORT NRG EC LOBBY)
Actual: 183 Pa (example)
Set point:
180 Pa (5)
or
VAR airflow control system
(VORT NRG EC MAC2
o
QUATTRO)
Actual: 4178 m3/h (example)
Set point:
5000 m3/h (5)
Air control
25
Содержание VORT NRG EC 3000
Страница 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Страница 38: ...ENGLISH BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 metres Ext Disp OU 38...
Страница 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Страница 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Страница 54: ...54 NOTE ENGLISH...
Страница 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Страница 85: ...FRAN AIS BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 m tres Ext Disp OU 85...
Страница 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Страница 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Страница 101: ...101 IX NOTE FRAN AIS...
Страница 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Страница 132: ...DEUTSCH BMS Standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 Meter Ext Disp OU 132...
Страница 133: ...DEUTSCH SIGNALVERST RKER RS485 100 Meter Max 6 Steuereinheiten MASTER Ext Disp SIGNALVERST RKER 133...
Страница 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Страница 148: ...148 IX NOTE DEUTSCH...