VI.6 Connection of pressure transmitters for MAC2 / LOBBY / QUATTRO
The pressure transmitters are factory-wired.
VI.7 Connection of CO
2
transmitter for DIVA / QUATTRO
The CO2 transmitter is factory-wired
VI.8 Bypass
This function is automatically controlled using the CORRIGO regulator’s programming and the probes installed as
standard in our VORT NRG EC units.
In winter (FREE HEATING):
When heat is required, the bypass closes to recover maximum calories through the plate
exchanger. If this recovery is not adequate to reach the temperature set-point, the water coil valve (if available) will open
or the electric coil (if available) will start.
In summer (FREE COOLING):
The bypass closes when the outside temperature is higher than the inside temperature
to prevent the outside heat from entering directly. If the outside temperature is lower than the inside temperature, the
bypass opens to get the cool outside air.
On the VORT NRG 6000-8000 models, the single servomotor is wired in the same manner as the small shutter.
ENGLISH
BR
O
W
N
W
HI
TE
G
RE
EN
BR
O
W
N
W
HI
TE
G
RE
EN
SUPPLY AIR
RETURN AIR
LOBBY / MAC2 AND QUATTRO EC
PRESSURE TRANSMITTER
BR
O
W
N
W
HI
TE
G
RE
EN
Bypass servomotor recovery
unit side
SMALL SHUTTER
NRG EC terminal
Bypass servomotor recovery
unit front
LARGE SHUTTER
19
Содержание VORT NRG EC 3000
Страница 37: ...X NOTES GRAPHS AND COMMUNICATION DIAGRAMS ENGLISH Date Observations 37...
Страница 38: ...ENGLISH BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 metres Ext Disp OU 38...
Страница 39: ...ENGLISH REPEATER RS485 100 metres Maximum 6 control units MASTER Ext Disp REPEATER 39...
Страница 40: ...ENGLISH BMS LON 100 metres MASTER Ext Disp LON EXTENSION OU 40...
Страница 54: ...54 NOTE ENGLISH...
Страница 84: ...X REMARQUES GRAPHIQUES ET DIAGRAMMES DE COMMUNICATION 84 FRAN AIS Date Observations...
Страница 85: ...FRAN AIS BMS standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 m tres Ext Disp OU 85...
Страница 86: ...FRAN AIS R P TEUR RS485 100 m tres Maximum 6 centrales MA TRE Ext Disp R P TEUR 86...
Страница 87: ...FRAN AIS BMS LON 100 m tres MASTER Ext Disp EXTENSION LON OU 87...
Страница 101: ...101 IX NOTE FRAN AIS...
Страница 131: ...X NOTIZEN SCHAUBILDER UND KOMMUNIKATIONSDIAGRAMME DEUTSCH Datum Anmerkungen 131...
Страница 132: ...DEUTSCH BMS Standard MODBUS RS485 WEB TCP IP BACNET TCP IP EXO TCP IP 100 Meter Ext Disp OU 132...
Страница 133: ...DEUTSCH SIGNALVERST RKER RS485 100 Meter Max 6 Steuereinheiten MASTER Ext Disp SIGNALVERST RKER 133...
Страница 134: ...DEUTSCH BMS LON 100 Meter MASTER Ext Disp ERWEITERUNG LON OU 134...
Страница 148: ...148 IX NOTE DEUTSCH...