background image

 

34 

 

 

5.2.8.  EPO terminals (X50).

 

 

 

•    All UPSs have two terminals to install an external emergency 

button to shutdown the output (EPO).

 

•    In case it was required to install a switch or button (EPO) in a 

single equipment, the cable bridge that closes the circuit has to 

be removed from terminal strip 

(X50) 

first.

 

•    For  a  parallel  system,  two different  solutions can be  applied, 

which are the following:

 

 

Connect  the  button  (EPO)  in  only  one  equipment  of  the 
parallel  system.  Remove  the  cable  bridge  from  terminals 

(X50)

 in the equipment that it is only connected. 

In  case  of  fault  and  removing  of  the  equipment  that  has 
physically connected the button (EPO), there is the risk of 
leaving the system without the emergency stopping, unless 
it is reconnected to the other operative UPSs.

 

 

Connect a button (EPO) to each equipment of the parallel

 

system.  To  do  that,  remove  all  the  cable  bridges  from 
terminals 

(X50) 

in each equipment. 

Therefore, the functionality of the (EPO) will be kept in each 

one  of  them,  regardless  what  occurs  in  the  rest  of 

equipment

 of the parallel system. 

By  means  of  the  own  communication  BUS  among  the 

equipment

 that make the parallel system, any action over any 

button will affect to the whole. 

•    In any case, the switch or button (EPO) has to be normally closed 

(NC), so the emergency shutdown order will be triggered when 
opening the circuit between these terminals 

(X50)

.

 

To restore the UPS to normal mode, invert the position of the 
switch or button (EPO), -close the circuit between the terminals 

(X50)

-, unblock the button.

 

•    To know the operating of (EPO), see section 6.6. of this manual.

 

•    The base of front door 

(PF) 

has a slot to facilitate the entering and 

way out of the communication cables inside the UPS. Watch to not 
trap them between the door and cabinet when closing it.

 

 

 

(X50) 

  EPO 
(Output

 

Emergency

 

Shutdown)

 

 

 
 
 
 

 

Fig. 31.   

Connection terminals for emergency shutdown switch or 

button (EPO), belonging to the end/user.

 

 

 

5.2.9.  Auxiliary contact and battery temperature 

probe terminal strip.

 

 

•    All  the 

equipment  are  provided  with  terminal  strip  that 

corresponds to the auxiliary contacts of manual bypass 

(X51) 

and output 

(X45) 

switches. 

•    Also  in  the  equipment  either  with  separate  batte

ry  cabinet

 

(models  >20  kVA  (LV)  /  >40  kVA  (HV)),  the  additional 

terminal  strip 

(X34) 

are  supplied,  to  connect  the  battery 

temperature probe that allows compensating the floating voltage 
according to the ambient temperature.

 

•    Any wire connected to the terminals 

(X34)

(X45) 

and 

(X51)

, will 

be entered into the equipment through the cable bushing 

(PR)

.

 

 

5.2.9.1.  Terminal strip, auxiliary contact of manual 

bypass switch (X51).

 

.

 

•    Terminal  strip 

(X51) 

of  two  pins  of  the  UPS,  is  connected  in 

parallel with the normally opened auxiliary contact of the switch 
or manual bypass switch of the equipment. 

•  Switchgear  panel board  with  manual  bypass  manufactured  by 

us (option), there is a terminal strip of two terminals connected 
in  parallel  with  the  normally  opened  auxiliary  contact  of  the 
switch or manual bypass switch of the own switchgear panel 
board. Any auxiliary contact of the manual bypass are moved on 
in advance when closing.

 

 

•  

   

In  case  of  acquiring  a  switchgear  panel  board 

with manual bypass in another way, check that it has

 

the  stated  auxiliary  contact  and  connect  it  to  the 
terminal  strip  (X51)  of  each  equipment.  As  a  must,  the 
auxiliary contact has  to  be  moved on  in  advance when 

closing.

 

 

•   

 

It  is 

ESSENTIAL 

as  safety  measure  of  the  system, 

loads included, to connect the terminal strips 

(X51) 

of

 

the UPSs with the terminal strip with the same functionality of 
the  switchgear  panel  board. 

This  way,  any  wrong  action 

over any switch or manual bypass switch of the turned 
on UPSs will avoid causing a total or partial fault of the 
installation, loads included.

 

 

5.2.9.2. Terminal strip, auxiliary contact of output 
switch (X45).

 

 

•    This terminal strip of two pins is available in any equipment, but 

it is useful in parallel systems only.

 

•    Basically, the normally  opened auxiliary contact of the  output 

switch,  is  extended  till  the  terminal  strip  of  two  pins 

(X45)

Through  the  isolated

  cable  as  a  bridge  mode  that  is  supplied 

connected  between  both  pins,  the  circuit  is  closed.  Do  not 
remove  in  single  equipment,  because  although  the  equipment 
would be in operation, there would be an alarm of output switch 
deactivated. 

•    In those installations with parallel systems, the cable as a bridge 

mode  connected  between  the  two  pins  of  the  terminal  strip 

(X45) 

of  each  UPS  has  to  be  removed,  and  connected  to  the 

terminals  corresponding  to  the  auxiliary  contact  of  the  output 
switch of the switchgear panel board. 

 

•  

   

In case of acquiring a switchgear panel board by 

yourself, check if the output auxiliary contact is 
available and connect it to the terminal strip (X45) of 
each equipment. As a must, the auxiliary contact has to 
be moved on in advance when opening.

 

Содержание Taurus UPS-10

Страница 1: ...7 Touch LCD Online UPS 208V 7 5K 60KVA 400V 10K 200KVA Uninterruptible Power Supply System User Manual...

Страница 2: ...X4 5 2 2 Connection of separate static bypass line terminals X14 a X17 UPS B version only 5 2 3 Connection to the output terminals X6 to X9 5 2 4 Connection to the battery terminals of the equipment...

Страница 3: ...hand during the installation and commissioning procedures In the next pages the equipment or unit and S T S terms are referred to the Uninterruptible Power Supply UPS and Service and Technical Support...

Страница 4: ...urrent a c Direct current d c 2 1 2 For more information and or help For more information and or help of your specific unit request it to our Service and Technical Support S T S 2 2 SAFETY INSTRUCTION...

Страница 5: ...any installation task Do not store install or expose the equipment in corrosive wets warm dusty environments or with conductive parts and never outdoors The best location for installation should be c...

Страница 6: ...ration Once the respective actions are completed recover the equipment to it was with the protection cover put back and front door closed To shut down the equipment completely follow the instructions...

Страница 7: ...ied personnel who will be responsible for applying the safety and EMC regulations and standards controlling the particular installations and the place where the product is destined 2 2 3 Safety warnin...

Страница 8: ...particular due to this last period and safety reasons the energy generator should be handled with care especially to prevent batteries from unnecessarily discharging during these periods of time When...

Страница 9: ...ers EN IEC 60950 1 IT equipment Safety Part 1 General requirements EN IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requirements The manufacturer s responsibility excluded the event of any m...

Страница 10: ...of the same family because the necessary electronic kit is included Connection in parallel can be done at any time when the upgrading requirements are needed to increase the supplied power of the equi...

Страница 11: ...from 7 5 to 30 kVA LV 10to 60 kVA HV with or without separate static bypass line B Fig 2 UPSfrontview from 40 to60kVA LV 80 to120kVA HV without separate static bypass and 40 kVA LV 80 kVA HV with sep...

Страница 12: ...CD Touch Screen View 1 Equipment with extended back up time only Fig 4 UPS Front view with door opened 7 5KVA to 20KVA LV 10KVA to 40KVA HV models Fig 5 UPS Front view with door opened 30KVA LV 60KVA...

Страница 13: ...iew with door opened 7 5KVA to 10KVA LV 10KVA to 20KVA HV models with separate static bypass line UPS B models Fig 7 UPS Front view with door opened 15KVA LV 30KVA HV models with separate static bypas...

Страница 14: ...12 Fig 8 UPS Front view with door opened models 20KVA LV 40KVA HV with separate static bypass line UPS B models Fig 9 UPS front view with door opened models 40kVA LV 80KVA HV...

Страница 15: ...13 Fig 10 UPS front view with door opened models 50 and 60 kVA LV 100 and 120 kVA HV without separatestatic bypass line...

Страница 16: ...14 Fig 11 UPS front view with door opened models 80 and 100 kVA LV 160 and 200 kVA HV without separatestatic bypass line...

Страница 17: ...15 Q8 X47 X49 X48 BF X5 PR X10 Fig 12 Battery cabinet front view No 1 with door closed Fig 13 Battery cabinet front view No 1 with door opened...

Страница 18: ...16 Q8 X47 X49 X48 X5 PR X10 Fig 14 Battery cabinet front view No 2 with door closed Fig 15 Battery cabinet front view No 2 with door opened...

Страница 19: ...17 Fig 16 Battery cabinet front view No 3 with door closed Fig 17 Battery cabinet front view No 3 with door opened...

Страница 20: ...static bypass phase R B version only X15 Terminal of static bypass phase S B version only X16 Terminal of static bypass phase T B version only X17 Terminal of static bypass neutral N B version only 1...

Страница 21: ...ng BL of switch Q5 By means of the connectors X36 and X36 the communication loop or ring is closed between two or more equipment connected in parallel by means of the bundle BC These connectors are no...

Страница 22: ...s it is used to filter the DC needed for the correct operation of PFC converter and inverter 4 3 3 Batteries This UPS series has a battery set that stores energy during the normal operating mode prese...

Страница 23: ...hem The bypass stage is based on six double thyristors in semipack format working as AC switches three of them are for shifting the input over the output and the other three are for shifting the inver...

Страница 24: ...consigning a battery discharging current even with existing mains This quality performance will make it possible to do a battery test both in full load and in no load conditions Output three phase rec...

Страница 25: ...d in the previous section 4 4 1 Normal operating 4 4 3 Operating with non active inverter The inverter is non active due to alarm conditions like overloads over temperatures etc In this case the recti...

Страница 26: ...W N Inp Out COM connections Inp Out Fig 22 Single line diagram connection of parallel system up to 4 units of UPS models COM connections Inp Out R S T N R S T N COM connections U V W N Inp Out COM con...

Страница 27: ...ures a quality of AC power supply for the most critical loads The quantity of redundant equipment to be connected has to be studied according to the requirements of the application No matter Parallel...

Страница 28: ...attached to the impact indicator located on the packaging Unpacking Check the content before deserting the packaging Unpack the package according to the Unpacking procedure in the supplied document in...

Страница 29: ...nce of the floor kg m2 25 cm 25 cm 150 cm 25 cm 25 cm 5 1 4 Location immobilization and considerations 5 1 4 1 Location for single equipment As i e Fig 24 itshows two typical cases depending on the mo...

Страница 30: ...ion referred to the installation of a single equipment or parallel system Switchgear or external manual bypass panel boards It is advisable to have an external manual bypass panel board equipped with...

Страница 31: ...r power rate are supplied in a separate cabinet Therefore battery protection is arranged as follows In the UPS stated in this document as Q3 Battery fuse holder switch with 3 fuses in models up to 20...

Страница 32: ...ipment Connection to three phase mains Connect the power supply cables R S T N to the input terminals X1 X2 X3 and X4 respecting the phase rotation and neutral indicated on the label of the equipment...

Страница 33: ...loads to U V W N output terminals X6 X7 X8 and X9 respecting the phase rotation and neutral indicated on the label of the equipment and in this manual If the phase rotation is not respected the equip...

Страница 34: ...ng one side to terminals X11 X23 and X12 of UPS and the other one to terminals X47 X49 and X48 of battery module always respecting the stated polarity on the labelling of each element and this manual...

Страница 35: ...a communication cable of just 3 wires Physical structure of the RS 232 Pin 2 RXD Serial data reception Pin 3 TXD Serial data transmission Pin 5 GND Ground signal Physical structure of the RS 485 Unli...

Страница 36: ...that allows compensating the floating voltage according to the ambient temperature Any wire connected to the terminals X34 X45 and X51 will be entered into the equipment through the cable bushing PR...

Страница 37: ...cation BUS To do it connect them in a sequential way two lines of the communication BUS between a unit and its adjacent Together with each UPS of a parallel system it is supplied a 15 wires bundle wit...

Страница 38: ...ts to be a guide to clarify the possible doubts on how the communication loop has to be connected To see the physical layout of the COM connectors for each power rate refer to the illustrations of fig...

Страница 39: ...n mean while the input voltage is available In those installations without the external manual bypass panel board omit the actions and steps that involve the maneuvering of their switches Fig 33 Proce...

Страница 40: ...UPS in the system Turn the input switch Q1a to On position for each UPS in the system Each display of the Control Panel will be turned on automatically Do not close any other switches at this time Re...

Страница 41: ...trol panel Turn the output switch Q2 of the UPS On 6 5 COMPLETE SHUTDOWN OF THE UPS Shutdown the loads If the system has outgoing distribution protections switch them Off Shutdown the inverter Please...

Страница 42: ...maintenance bypass to normal operation In model with external battery cabinet set fuse holder switch from battery cabinet Q8 to On position In standard units set the input switch Q1a to On position I...

Страница 43: ...home from any screen of any submenu we can go back to main screen Screen 0 0 Fig 35 Screen 0 0 Main Screen 7 2 2 CONTROL Level screen menu 1 0 Screens 1 1 and Screen 1 2 It s to start and stop the un...

Страница 44: ...about the battery test is given Possible messages EXECUTING The battery test is running SUCCESSFUL The battery test has been successful NOT SUCCESSFUL The battery test has not been successful Screen...

Страница 45: ...urrent for three phase equipment per phase for single phase equipment accuracy 0 1A Charging Current Positive and negative accuracy 0 1A Discharging Current Positive and negative accuracy 0 1A Screen...

Страница 46: ...he options are the following SEC MODBUS Screen 3 3 Automatic battery test setting The options for the Type to be programmed are the following DISABLED The automatic battery test is disabled WEEKLY The...

Страница 47: ...this level an authorized password will be required to modify some advanced parameters If you need to modify advanced setting please check with your dealer to get password Screen 3 5 Rated Value To mod...

Страница 48: ...m appears when the input the unit is under main failure condition and the level of battery is lower than 11 5V bat Alarm 4 This alarm appears when the inverter output voltage phase to neutral in any p...

Страница 49: ...op UPS Stop 71 Parallel System UPS Stop 72 Emergency Power Off No Output Voltage BYP STOPS 38 Output Short circuit No Output Voltage 39 DSP Internal Error UPS Block All 40 DC BUS Voltage Wrong Rectifi...

Страница 50: ...l be blocked after 30 and a blocking alarm 61 will appear Alarm 33 This alarm appears when there is a DSP Internal Error in the inverter module shutting down the inverter immediately There will be 4 m...

Страница 51: ...ed Alarm 64 If there is a blocking condition for the inverter and also a blocking condition for the PFC this alarm appears blocking also the UPS Alarm 65 This alarm can be activated due to a connectio...

Страница 52: ...as already been chosen as a Fix Master in the system a second error or break in the communications has been detected by the Slaves equipment which will be blocked permanently Rectifier and Inverter ar...

Страница 53: ...tween 3 and 7 years if the ambient temperature is between 10 and 20 C To have more information of its status activate the battery test Risk of fire and or explosion exists if a wrong quantity or type...

Страница 54: ...rest factor 3 4 to 1 3 2 to 1 2 8 to 1 3 2 to 1 3 to 1 Permissible power factor 0 7 leading to 0 7 lagging Unbalancedoutputvoltage 100 unbalancedload 1 Current limit High overload short circuit RMS vo...

Страница 55: ...d THD i 5 0 100 load THD i 1 5 50 load THD i 2 0 10 load THD i 6 0 Current limit High overload PFC limit discharging batteries Power factor 0 99 from 10 load INVERTER Output nominal voltage Single pha...

Страница 56: ...UPS CONFIGURATIONS WITH STANDARD BACK UP TIME Quantity of cabinets 1 UPS batteries 1 UPS 1 batteries Maximum dimensions mm Depth x Width x Height UPS UPS B1 770x450x110 875x590x1320 850x900x1900 UPS B...

Страница 57: ...uit through which are sent or received signals from a system or subsystems toward others kVA The voltampere is the unit of the apparent power in electrical current In direct current is almost equal to...

Отзывы: