background image

15

5.1

GAS SUPPLY INSTALLATION

Inspect the entire installation including the gas
meter, test for soundness and purge. Refer to BS
6891 for specific instruction.

5.2

THE HEATING SYSTEM

The appliance contains components that may
become damaged or rendered inoperable by oils
and/or debris that are residual from the installation
of the system, consequently it is essential that the
system be flushed in accordance with the follow-
ing instructions.

5.3

INITIAL FILLING OF THE SYSTEM

Ensure both flow and return service valves are
open, remove appliance casing as described in
4.7.1, identify the automatic air release valves
(AAV) and loosen the dust cap/s by turning the cap
anti-clockwise one full turn.

IMPORTANT, THERE ARE NO MANUAL AIR
RELEASE VALVES LOCATED ON THE APPLI-
ANCE

. Ensure all manual air release valves lo-

cated on the heating system are closed.
Connect the filling loop as shown in fig. 5, slowly
proceed to fill the system by firstly opening the
inlet valve connected to the flow pipe, and then
turning the lever on the fill valve, to the open
position. As water enters the system the pressure
gauge will begin to rise. Once the gauge has
reached 1 BAR close both valves and begin
venting all manual air release valves, starting at
the lowest first. It may be necessary to go back
and top-up the pressure until the entire system has
been filled. Inspect the system for water sound-
ness, rectifying any leaks.

5.4

INITIAL FLUSHING OF THE SYSTEM

The whole of the heating system must be flushed
both cold and hot as detailed in 5.8. Open all
radiator or heating valves and the appliance flow &
return service valve. Drain the boiler and system
from the lowest points Open the drain valve full
bore to remove any installation debris from the
boiler prior to lighting. Refill the boiler and heating
system as described in 5.3.

5.5

PRE-OPERATION CHECKS

Before attempting the initial lighting of the appli-
ance, the following checks must be carried out:

ensure all gas service valves from the meter to
the appliance are open and the supply pipe has
been properly purged;

ensure the proper electrical checks have been
carried out, (see 7.8) particularly continuity,
polarity and resistance to earth;

ensure the 3 AMP fuse - supplied with the
appliance - has been fitted;

ensure the system has been filled, vented, and
the pressure set to 1 BAR;

ensure the flue system has been fitted properly
and in accordance with the instructions;

ensure all appliance service valves are open.

5.6

INITIAL LIGHTING

Ensure the electrical supply to the appliance is
switched on. Press the ON/OFF switch to switch
the appliance ON (indicated by active display),
ensure any external controls are switched to an
‘ON’ position and are calling for hea.
Press the function button and select “Winter mode”,
the appliance will now operate in the “Winter mode”
as described in 1.2. Should the appliance fail to
ignite, refer to 5.6 and/or section 7 (mode of
operation, parameter setting, & faultfinding).

5.7

CHECKING GAS PRESSURE AND COMBUS-
TION ANALYSIS

The appliance is factory set and should require no
additional adjustment once installed. However, if
the gas valve has been adjusted, or the appliance
has been converted for use with another gas type,
then it’s necessary to carry out a combustion
analysis/check to ensure that correct combustion
is occurring. Details on how to carry out the
combustion analysis can be found in section 7.

IMPORTANT

It’s imperative that a sufficient dynamic - gas -
pressure is maintained at all times. Should the
dynamic gas pressure fall below an acceptable
level, the appliance may malfunction or sustain
damage.

5.8

FINAL FLUSHING OF THE HEATING SYSTEM

The system shall be flushed in accordance with
BS 7593. Should a cleanser be used, it must be
suitable for Copper and Aluminium heat exchang-
ers. It shall be from a reputable manufacturer and
shall be administered in strict accordance with the
manufacturers’ instructions and the DWTA code
of practice.

5.8.1

INHIBITORS

See Section 3 “General Requirements”.

5.9

SETTING THE BOILER OPERATING TEMPERA-
TURE

The flow outlet temperature can be adjusted be-
tween 20 °C - 80 °C via the Heating thermostat
knob (see fig.1).

5.9.1

INFORMATION MODE

The appliance keypad can be used to display
certain information on the working status of the
boiler. Push the Info button ( ) to enter the info
menu (fig. 17).

SECTION 5      COMMISSIONING

Fig. 17

Содержание MYNUTE 35HE

Страница 1: ...Installation Servicing Instructions THESEINSTRUCTIONS TO BE RETAINED BY USER 0694 0694BQ0479...

Страница 2: ...on analysis 15 5 8 Final flushing of the heating system 15 5 9 Setting the boiler operating temperature 15 5 10 Setting the system design pressure 16 5 11 Regulating the central heating system 16 5 12...

Страница 3: ...ansion ves sel safety valve pressure gauge and automatic by pass The35HEisproducedasaroomsealed categoryII2H3P appliance suitableforinternalwallmountingapplications only It is provided with a fan powe...

Страница 4: ...try to ensure flame stability at the burner Once suc cessful ignition has been achieved the electronic circuitryincreasesthegasrateto75 foraperiod of 15 minutes Thereafter the boiler s output will eit...

Страница 5: ...ions Height 845 mm Width 453 mm Depth 359 mm Dry weight Kg 43 0 2 5 Clearances Sides 12 mm Top 150 mm from casing or 25 mm above flue elbow whichever is applicable Bottom 150 mm Front 600 mm 2 6 Conne...

Страница 6: ...tc 500 mm D Below gutter drain pipe etc 75 mm E Below eaves 200 mm F Below balcony car port roof etc 1200 mm G To the side of a soil drain pipe etc 150 mm H From internal external corner or boundary 3...

Страница 7: ...entrally over the terminal Refer to BS 5440 Part 1 when the terminal is 0 5 metres or less below plastic guttering or 1 metre or less below painted eaves BS5440 PART 1 FLUES BS5440 PART 2 FLUES VENTIL...

Страница 8: ...fuse The method of connection to the mains electricity supply must allow for com plete isolation from the supply The preferred method is by using a double pole switch with a contact separation of at...

Страница 9: ...hosenfortheappliancemustpermit the provision of a safe and satisfactory flue and termination The location must also permit an adequateairsupplyforcombustionpurposesand anadequatespaceforservicingandai...

Страница 10: ...he system has an unusually high water content it may be necessary to provide additional expansion capacity see 6 19 3A 6 6 FILLING POINT Amethodforinitialfillingofthesystemandreplacing water lost duri...

Страница 11: ...te supplied carefully mark the position of the wall mounting bracket see fig 6 and flue hole if applicable 4 5 FITTING THE FLUE The top flue outlet permits both horizontal and verticalflueapplications...

Страница 12: ...to ensurethatthecorrectsealismadewhenassem blingthefluesystem Connecttherequirednumber of flue extensions or bends up to the maximum equivalentfluelength totheflueterminal seefig 7 8 The flue system...

Страница 13: ...the dedi cated concentric flue kit for termination It is essential that the installation of the twin flue system be carried out in strict accordance with these instructions GUIDANCE NOTES ONTWIN FLUE...

Страница 14: ...in flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter NOTE Seal the flue terminal assembly to the wall using cement or a suitable alternative that will provide sa...

Страница 15: ...nlet of the valve and tighten both nuts NOTE Itwillbenecessarytocalculatethediameterofthe gas supply pipe to ensure the appliance has an adequate supply of gas 4 6 2 FLOW RETURN fig 6 The appliance is...

Страница 16: ...B cover C Fig 15 Optional devices 24V terminal block Mains 230V terminal block 4 7 2 APPLIANCETERMINALBLOCK Theapplianceterminalblockislocatedontherear of the control fascia Remove the casing as descr...

Страница 17: ...ensure the proper electrical checks have been carried out see 7 8 particularly continuity polarity and resistance to earth ensure the 3 AMP fuse supplied with the appliance has been fitted ensure the...

Страница 18: ...LY SECURED ENSURE ALL PIPE WORK IS RE CHECKED FORSOUNDNESS RE FIT APPLIANCE CASING COMPLETEBENCHMARKCHECKLIST FOR UK ONLY Complete details of the boiler controls installa tionandcommissioningintheBenc...

Страница 19: ...ugh it is anticipated that this appliance will give years of reliable trouble free service the life spanofcomponentswillbedeterminedbyfactors such as operating conditions and usage Should the applianc...

Страница 20: ...rolfasciaupwardandrotate it Locateandremovethescrews A whichsecure the PCBcover pushtheclips B andremovecover after carefullytakingnoteofallwiringconnections discon nect all wiring from the PCB locate...

Страница 21: ...re it is replaced correctly Replace in the reverse order 6 16 MAIN HEAT EXCHANGER fig 29 30 Carry out component removal procedure as de scribed in 6 4 Unclip and remove the three air chambercovers fro...

Страница 22: ...tandleft side covers Disconnect the fan transformer wiring Locateandremovethe2screws D thatsecurethefan transformer to the air box plate cut the two cable ties previewedonheat shrinkableinsulatorsthat...

Страница 23: ...of the primary thermistor reaches 30 C There after the pump fan will over run for 30 sec onds Pump anti block cycle when there has been noheatingorHWrequestfor24 hours theanti block cycle is activate...

Страница 24: ...ee fig 36 Push MODE button and selecttheadjustparameterspasswordbyturning the RH right hand encoder and confirm it by pushingMODEbutton Thefollowingfunctionsare available in this mode 7 4 1 GAS TYPE S...

Страница 25: ...liance however you must check that the CO2 values are set correctly see 7 4 Insert the flue gas analyser probe into the flue gas test point see fig 35 Operate the boiler in HH LL and compare the value...

Страница 26: ...ition 13 check the wiring harness 23 check the wiring harness 25 high limit flow temperature probe 27 high limit return temperature probe 31 internal fault 35 fan error 36 internal fault 41 low water...

Страница 27: ...odes 6x appear if a problem exists with the secondary DHW thermistor Check thermistor Check wiring continuity FAULT CODES 5x Fault codes 5x appear if a problem with the main board exists Check paramet...

Страница 28: ...3600 1 25 Differential heating positive C 2 10 1 6 26 Differential heating negative C 2 10 1 6 28 CH timer force burner 75 after CH start Min 0 20 1 15 29 CH timer blocking time CH Min 0 20 1 5 30 CH...

Страница 29: ...win channel programmers figs 40 41 The appliance can be used in conjunction with typi cal S Plan Y Plansystems see8 4 1 8 4 2 please contact Vokera technical should you requirefurtherdetailedinstructi...

Страница 30: ...28 8 4 1 Y PLANWITH EXTERNALTWIN CHANNEL PROGRAMMER fig 40 8 4 2 S PLANWITH EXTERNALTWIN CHANNEL PROGRAMMER fig 41 Fig 40 Fig 41...

Страница 31: ...S Outside sensor WPS Water pressure sensor FS Flow termoster RS Return termoster AE01A P1 Master board AE01A P2 Ausiliary board controll M0T2B Motor control board AC0X Display board K9 Pump relay K13...

Страница 32: ...cover assembly 10025842 26 Instrumental panel 10027949 31 Case 10026241 38 Driver PCB 10027200 90 Fuse 3478 226 Edge clip 5128 300 Wiring harness 10026341 301 Wiring harness 10027953 302 Wiring harnes...

Страница 33: ...ctions cover 10027685 63 Pipe 10026228 105 Pressure transductor 10027132 201 Washer 5026 265 Washer 5236 266 Washer 5237 288 Washer 6898 290 Clip 2165 351 Nut 1823 353 Nut 1824 432 Clip 10024958 435 C...

Страница 34: ...6338 6 Pipe 10026264 7 Pipe 10027317 9 Pipe 10027318 10 Pipe 10027146 17 Air vent bottle 10026275 25 Siphon 10027190 26 Flexible pipe 10027191 27 Flexible pipe 10027192 48 Pipe 10027321 66 Flexible pi...

Страница 35: ...veyor 10026309 39 Gas pipe 10027196 46 Gas diaphragm 10027162 46 Gas diaphragm 2111 67 Washer 10026322 69 Tryton 10027089 72 Mixer 10024295 200 Washer 5023 479 Transformer 10026237 480 Transformer 100...

Страница 36: ...r assembly 01005369 7 Conveyor assembly 10026310 12 Flue drain connection 10026311 27 Fumes testing connection screw 10020625 475 Washer 10026323 482 Washer 10026366 487 Washer 10026345 509 Limit ther...

Страница 37: ...themaximumpower the CO2 readingshouldbeasshowninthetableabove If the CO2 reading is correct press the MODE button to exit the maximum setting If the CO2 reading is incorrect the maximum gas pressure m...

Страница 38: ...OW RATE lts min FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS YES FOR ALL INSTALLATIONS CONFIRM THE FOLLO...

Страница 39: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No...

Страница 40: ...0 333 0520 Fax 01442 281403 After Sales Service Tel 0870 333 0220 Vok ra Ireland West Court Callan Co Kilkenny Tel 05677 55057 Fax 05677 55060 Vok ra Ltd reserve the right to change the specifications...

Отзывы: