CONDEXA PRO
31
20
20
50
50 20
50 20
20
20
50
230 mm
90 mm
20
20
50
50
160 mm
Square compartment
Rectangular compartment
Minimum dimensions of the compartment
for the passage of three flues, diameter 50 mm
20
20
20
90 mm
160 mm
20
20
20
50
50
20
20
50
Ø 160 mm
20
20
50
50
Circular compartment
Rectangular compartment
Minimum inside dimensions of the compartment
for the passage of 2 flues, diameter 50 mm
20
50mm
50mm
63 mm
71 mm
Minimum inside dimensions of the compartment
for the passage of 1 flue, diameter 50 mm
Circular compartment
Square compartment
MAXIMUM LENGTH OF THE PIPES
The maximum equivalent length of the sum of the 50 mm
intake pipes and flues is 30 metres, with a pressure drop
of 2 metres for each 90° bend.
Installation of a single boiler with flue passing inside
a compartment (open flue operation).
For this type of operation, make sure that the size of the
compartment complies with the standards in force.
The figure on the side shows the minimum dimensions of
the compartment when passing one flue (model 50 M) or
two flues (models 100 M or 100 S).
b
Parameter 36 (see page 59) needs to be set based
on the type of gas and the length of the chimney.
model 50 M
models 50 M + 100 S
model 100 M