Installation Manual

Wall-mounted condensing boiler

srpski

Installation Manual

Wall-mounted condensing boiler

D2CNL024A1AA

Содержание D2CNL024A1AA

Страница 1: ...Installation Manual Wall mounted condensing boiler srpski Installation Manual Wall mounted condensing boiler D2CNL024A1AA...

Страница 2: ...atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem u...

Страница 3: ...separate and the plastics are marked This allows the various components to be sorted for appropriate recycling or disposal Jedinice su ozna ene slede im simbolom To zna i da se elektri ni i elektrons...

Страница 4: ...s otherwise stated or have the such performed by unauthorised third parties Otherwise the unit warranty becomes void OPASNOST Isolate the boiler from the power mains before working on it UPOZORENJE Un...

Страница 5: ...ating circuit to avoid air traps and consequent operational problems Frost protection safety system This function protects the unit and heating installation from frost damages It is controlled by the...

Страница 6: ...valve motor g Domestic hot water temperature sensor h Plate heat exchanger i Safety valve 3 bar j Condensate trap k Ignition transformer l Flue gas temperature sensor m Burner hood n Ignition electro...

Страница 7: ...products temp at nominal heat input C 90 CO2 Emission at nominal and minimum heat input G20 8 7 9 3 0 2 NOx Class 6 Energy related products ErP specifications Symbol Unit D2CNL024A1AA Model D2CNL024 C...

Страница 8: ...fied competent persons are allowed to open the unit Certain actions explained in this document such as gas conversion optional equipment connection require that the front cover is opened 1 Loosen the...

Страница 9: ...room containing a bath or a shower then particular reference is drawn to the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake...

Страница 10: ...elated system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charge pressure...

Страница 11: ...lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 0 0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700 800 900 1000...

Страница 12: ...system must be air free to protect the boiler There are two automatic air vents on the boiler one at heat exchanger the other on the pump Ensure air is discharged completely at each water filling Blee...

Страница 13: ...al equipment is connected to the connectors which are located on the outside of the switch box Do not open the switch box to connect optional equipment Temperature control units Connector Connectio n...

Страница 14: ...07 4 8 6 Wiring diagram OPASNOST RIZIK OD ELEKTROKUCIJE Disconnect the power supply for more than 10 minutes before servicing X1A X2 X4 X5 X1M X2M X6A X7 1 1 1 1 1 1 1 1 1 1 1 1 1 X12 X10 X11 X17 X15...

Страница 15: ...idelines when connecting the condensate piping OPASNOST In order to prevent escape of flue gases and so poisoning the condensate trap must be mounted to its place before commissioning Condensate trap...

Страница 16: ...It is essential to ensure that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infil...

Страница 17: ...rom separate combustion and air supply circuits shall fit inside a square of 50 cm and the distance between the planes of the two orifices shall be less than 50 cm a b e c c d d f g h L i a Roof termi...

Страница 18: ...ntric flue system INFORMACIJA C63 flue type is not applicable to Belgium To install the boiler as a C63x option the following data must be used to determine the correct diameters and lengths of the fl...

Страница 19: ...GP4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKFGP4802 Tile roof outlet kit 60 100...

Страница 20: ...sure reaches 0 8 bar again 9 Check the central heating circuit especially the couplings of the circuit for leakage 10 Isolate the unit from power mains 5 Commissioning UPOZORENJE Only qualified person...

Страница 21: ...Check the CO2 values at minimum capacity 5 Press CH to switch to maximum capacity H caption will appear on screen Check the CO2 values at maximum capacity 6 To quit sweeper mode press Reset button The...

Страница 22: ...unction of the boiler error mode Emphasise that if an error is indicated refer to Error codes in the operation manual Inform the user about frost protection function and advise never to cut off the el...

Страница 23: ......

Страница 24: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P469346 12P 2020 07 Copyright 2...