CONDEXA PRO
30
The
Vokera CONDEXA PRO
Boiler must be connected
to the natural gas or LPG supply in compliance with the
relevant standards in force.
Before making the connections, check that:
- the type of gas is the same that the appliance is set for
- the pipes are thoroughly clean
- the gas supply pipes are the same size or larger than
the fitting on the boiler (3/4"), with a pressure drop that
is less than the pressure drop between the gas supply
and the appliance.
When installation is completed, check that the joints are
all tight, as required by the installation standards.
A suitable filter should be installed on the gas line.
The flue and the fitting to the flue must be made in com-
pliance with the standards and the legislation in force, as
well as with local regulations.
The pipes used must be rigid and resistant to tempera-
ture, condensate and mechanical stress, and airtight.
b
Non-insulated flues are potential sources of danger.
A
S
A
S
61
275
37
275
212
C63
B23
B23
Fan upstream. Combustion air intake directly
from the room where the boiler is installed. Flue
gas exhaust through horizontal or vertical pipes,
fitted with ventilation openings.
C63
Fan upstream. Combustion air intake and flue
gas exhaust without terminals.
b
Please refer to any current standards and law
applicable to flues and ventilation.
A - Air intake Ø 50 mm
(Conversion kit for room-sealed operation
CONDEXA PRO
50
code 5037685135067
Conversion kit for room-sealed operation
CONDEXA PRO
100
code 5037685135074)
S - Flue Ø 50 mm
FUEL CONNECTIONS
FLUE GAS OUTLET AND COMBUSTION AIR INTAKE