Manual VIPA System 300V
Chapter 4 Deployment CP 343-2P ASI
HB130E - CP - RE_343-2AH10 - Rev. 08/41
4-5
By activation of this checkbox the diagnostic interrupt for the CP is
enabled. If enabled the following events may release a diagnostic interrupt:
•
Change of AS-i slave configuration in
protected mode
•
Loss of AS-i power supply
•
Error at Flash-ROM
The reaction on the variety of errors may be programmed in the OB 82.
When enabled and the AS-i master is in
protected mode
, a failed AS-i
slave may simply be replaced with a AS-i slave with address 0.
In this case, the AS-i master will automatically assign the address of the
replaced AS-i slave to the new AS-i slave.
This register shows the configuration of the AS-i bus. If you have already
uploaded a configuration made by "button configuration" into your project,
this may be checked respectively modified here.
Via double click to a line of the table a dialog window is opened. There the
corresponding AS-i slave may be configured. More may be found at
"Configuration AS-i slave".
The configuration, stored in the Flash-ROM of the CP, may be uploaded to
your project by clicking to the button [Upload to PG]. More may be found at
"Uploading the current configuration to PG".
Operating
Parameters
Diagnostic Interrupt
Automatic Address
Programming
Slave
Configuration
AS-i slave options