Chapter 4 Deployment CP 343-2P ASI
Manual VIPA System 300V
4-2
HB130E - CP - RE_343-2AH10 - Rev. 08/41
Fast introduction
•
Configure a profile rail
•
Configure the CPU with modules
•
Configure as VIPA CP 343-2P ASI the Siemens CP with order number
6GK7 343-2AH10-0XA0.
•
Save and translate you project and transfer it to the CPU.
The actual configuration of the connected AS-i slaves is stored in the
internal Flash-ROM of the CP by means of the button configuration.
Please regard that there is no slave with address "0" connected.
•
Supply your system with power
•
Switch the CPU to "STOP"
•
Push the "SET" button
The transfer of the current configuration from the CP to your project
happens by means of the register "AS-i Slave Options" at the properties
dialog of the CP. The configuration is transferred to the project by the
button "Upload to PG". This configuration may be accessed by the register
"Slave Configuration". Here the configuration may be changed or further
configurations may be configured based on this configuration.
Depending on the slave type there are the following possibilities for access
with the user program:
Access to ...
Type A/B
(standard)
Type A
Type B
Binary data
Peripheral load and transfer instructions
X
X
SFC 58/59 (write/read: record set 150)
X
-
X
Analog data
SFC 58/59 (write/read: record set 140...147)
X
-
-
Note!
Please regard a configuration produced respectively modified by the
Siemens SIMATIC manager always has priority in relation to a button
configuration! At start-up of the CPU the CP gets its AS-i configuration
from the CPU. Here a possibly existing button configuration is overwritten.
Hardware
configuration
Button
configuration
Upload the current
configuration to
the PG for
changes if
necessary
Access by the