Chapter 4 Deployment CP 343-2P ASI
Manual VIPA System 300V
4-4
HB130E - CP - RE_343-2AH10 - Rev. 08/41
The properties of the CP may be accessed by a double click at the CP
within your project in the hardware configurator. The parameters of the
VIPA CP 343-2P ASI may be modified by the registers in the following
described.
The short description with the information below is identical to the shown
Information in the "hardware catalog" window.
Here the order number of the Siemens CP 343-2P is displayed. For project
engineering of the VIPA CP 343-2P ASI the Siemens CP with order
number 6GK7 343-2AH10-0XA0 is to be used.
This displays the designation of the CP, which may be changed. If the
designation is changed, the new designation appears in your project in the
configuration table.
In this part the purpose of the module may be entered.
By presetting a start address for the input respectively output area the
beginning of the address area of the CPU may be determined, which is
mapped by the CP. Here the CP occupies for input and output 16byte
each.
1 byte of the 16byte I/O address area is used by 2 A/B (standard)
respectively A slaves for binary-coded data.
With the process image a consistent image of the process signal may be
accessed during the program cycle.
If the field
process image
shows the entry "---" then the set address area is
outside the process image. The entry "OB1-PA" indicates that the set
address area is within the process image.
CP 343-2P ASI
Properties
General
Short Description
Order No.
Name
Comment
Addresses
Inputs / Outputs
Process image